Connext API Datapoints

Data points stored by default in the cloud and available in APIs as of Connext version 915.03.0.

Datapoint 

ID hexa­decimal 

Category 

Description 

Unit 

Section 

GEWASTEMP.GEM_GEWAS 

D0 

MEAS BOX 

plant temperature 

°C 

I100 Measured plant temperature at this moment. 

M105 The measured plant temperature. 

M105.1 The measured plant temperature. 

  

GEWASTEMP.GEWAS_RV 

D2 

MEAS BOX 

relative humidity 

M105 The calculated relative air humidity at the measured plant temperature. 

M105.1 The relative air humidity for the measured plant temperature. 

  

GEWASTEMP.GEWAS_VD 

D3 

MEAS BOX 

humidity deficit 

g/m³ 

M105 The calculated humidity deficit for the measured plant temperature. 

M105.1 The humidity deficit for the measured plant temperature. 

  

GEWASTEMP.GEWAS_VPD 

D4 

MEAS BOX 

VPD 

kPa 

M105 The calculated vapour pressure deficit for the measured plant temperature. The vapour pressure deficit is the difference between the vapour pressure in the crop's stomata and the vapour pressure in the greenhouse air. 

M105.1 The calculated vapour pressure deficit for the measured plant temperature. 

  

KASLBOX.AV_KAS 

104 

MEAS BOX 

absolute humidity 

g/m³ 

I100 Measured relative humidity or humidity deficit at this moment. 

M105 The absolute humidity. 

M105.1 The absolute humidity. 

  

KASLBOX.DAUWPUNT_KAS 

10E 

MEAS BOX 

Dew point 

°C 

M105 The calculated temperature whereby the humidity from the air condenses. If part of the plant is below this temperature, it will become 'become wet'. 

M105.1 The calculated temperature whereby the humidity from the air condenses. If part of the plant is below this temperature, it will become 'become wet'. 

  

KASLBOX.GEM_CO2 

10F 

MEAS BOX 

CO₂ 

ppm 

M105 The measured CO2 concentration. 

M105.1 The measured CO2 concentration. 

  

KASLBOX.GEM_KAS_RV 

110 

MEAS BOX 

relative humidity 

I100 Measured relative humidity or humidity deficit at this moment. 

M105 The relative air humidity. 

M105.1 The relative air humidity. 

  

KASLBOX.GEM_KAS_VD 

111 

MEAS BOX 

humidity deficit 

g/m³ 

I100 Measured relative humidity or humidity deficit at this moment. 

M105 The humidity deficit. 

M105.1 The humidity deficit. 

  

KASLBOX.GEM_KASNBOL 

112 

MEAS BOX 

Wet bulb temperature 

°C 

M105 The wet bulb temperature. 

M105.1 The measured wet bulb temperature. 

  

KASLBOX.GEM_KASTEMP 

113 

MEAS BOX 

temperature 

°C 

I100 The measured greenhouse temperature that is passed on to the controls. 

M105 The dry bulb temperature, so the greenhouse temperature. 

M105.1 The measured greenhouse temperature that is passed on to the controls. 

  

KASLBOX.MeasEnthalpy 

5DA0 

MEAS BOX 

Enthalpy 

kJ/kg 

M105 The measured enthalpy of the greenhouse air. 

  

KASLBOX.PLANT_TEMP 

127 

MEAS BOX 

temperature 

°C 

M105 The calculated temperature of the plant, stems and fruit in the shadow. 

M105.1 The calculated temperature of the plant, stems and fruit in the shadow. 

  

KASLBOX.RUWE_KASTEMP 

12C 

MEAS BOX 

greenhouse temperature 

°C 

M105.1 The measured greenhouse temperature at this moment. 

  

CPOMPSYS.GER_POMP_CAP 

148 

MOD COOL 

Act pump capacity 

I222 Actual pump capacity of the modulating cooling system. 

  

CPOMPSYS.POMP_STATE 

14C 

MOD COOL 

Pump status 

0=OFF 

1=ANTI STUCK PROT. 

2=DELAY OFF 

3=ON 

4=SWITCH DELAY 

5=HIGH SP 

  

I222 Indication of the pump(s) in the cooling system. 

  

MKOEL_IO.GEM_KOELW_TEMP 

163 

MOD COOL 

Meas cooling water temperature 

°C 

I222 Measured temperature of the cooling water in the cooling system. 

  

MOD_KOELS.BER_KOELW_TEMP 

165 

MOD COOL 

Calc cooling water temperature 

°C 

I222 Calculated temperature of the cooling water of the cooling system. 

  

VDC_STU.TOESTAND 

1C1 

PAD PUMP 

Status pad pump 

0=OFF 

1=ON 

  

I134 The status of the pad pump. 

  

REG_FAN.AANTAL_FAN_AKT 

20A 

F&P CONTR 

Number of active fan stages 

  

I130 The number of active fan stages by the calculated fan capacity and forced by for example curtains, rain, storm or frost. 

I133 The number of connected fan stages in the ON and FORCED ON statuses. 

M100 The measured number of active fan stages. 

M106 The measured number of active fan stages. 

M130 The number of active fan stages by the calculated fan capacity and forced by for example curtains, rain, storm or frost. 

  

REG_FAN.TOEST_FANR 

20D 

F&P CONTR 

Status fan control 

0=NOT ACTIVE 

1=ACTIVE 

2=SWITCH ON 

3=SWITCH OFF 

4=ROTATE 

  

I133  

  

REG_PEF.BER_VENT_CAP 

216 

F&P CONTR 

Calculated fan capacity 

I130 The degree to which F&P cooling is desirable. The calculated fan capacity determines the number of fan stages and the switching moment of the pad pump. 

M130 The degree to which F&P cooling is desirable. The calculated fan capacity determines the number of fan stages and the switching moment of the pad pump. 

  

REG_PEF.GEW_FAN_AKT 

218 

F&P CONTR 

Calc number of fan stages 

  

I130 The calculated maximum number of fan stages that is allowed to be active. 

M130 The calculated maximum number of fan stages that is allowed to be active. 

  

REG_PEF.PEF_AKTIEF 

221 

F&P CONTR 

fan and pad cooling active 

0=NO 

1=YES 

  

I130 Indication of whether the F&P cooling is active. 

M130 Indication of whether the F&P cooling is active. 

  

REG_PEF.REFERENTIE 

225 

F&P CONTR 

fan and pad cooling temperature 

°C 

M106  

  

REG_PEF.START_PEF 

226 

F&P CONTR 

fan and Pad cooling temperature 

°C 

I130 The calculated (greenhouse) temperature limit above which the F&P cooling becomes active. 

M106  

M130 The calculated (greenhouse) temperature limit above which the F&P cooling becomes active. 

  

VntsPBand.CalcPBand100p 

6348 

VENT.CONTR 

calculated P band 

°C 

M125.1 The calculated P band, depending on the set (minimum and maximum) P band, the weather influence on the P band and the increase & decrease time over which the vents are moved from 0% to 100%. 

  

KASL_REF.ATR_GEM_KAS_TEMP 

37D 

VENT.CONTR 

ventilation temperature 

°C 

I100 The measured ventilation temperature (greenhouse or plant temperature). 

M100 The measured ventilation temperature (greenhouse or plant temperature). 

  

VENTAFST.STW_RAAM 

4B0 

VENT.CONTR 

Calc ventilation temperature 

°C 

I120 The calculated ventilation temperature after influencing. 

I121  

M100 The calculated ventilation temperature. 

M100.1 The calculated ventilation temperature. 

M106  

  

VntsControl.ActAirExchange 

3A7 

VENT.CONTR 

Calc air exchange 

m³/(hr.m²) 

M120 The calculated air exchange for the ventilation control. 

  

VntsControl.MeasCtrlTemp 

4B4 

VENT.CONTR 

ventilation temperature 

°C 

M106  

  

VntsLeeSide.CalcMaxVentLee 

60BA 

VENT.CONTR 

Calculated max vent lee 

M125 The calculated maximum vent position for the lee side after possible limitations. 

  

VntsLeeSide.CalcMinVentLee 

417 

VENT.CONTR 

Calculated min vent lee 

M125 The calculated minimum vent position on the lee side. 

  

VntsLeeSide.CalcVentLeePos 

3D4 

VENT.CONTR 

Calculated vent lee 

M125 The calculated vent position on the lee side. 

  

VntsLeeSide.CalcVtTempLee 

60BD 

VENT.CONTR 

Calc ventilation temperature lee 

°C 

M120 As soon as the measured temperature rises above the ventilation temperature calculated here for the lee side, then on the lee side the vents will start to be controlled open. 

  

VntsLeeSide.CodeLimitMnLee 

60BF 

VENT.CONTR 

Limitation min vent lee 

0=NONE 

1=MIN 

2=CROP TREATM. 

3=CURTAIN 

4=ON/OFF HEAT 

5=RAIN 

6=FROST 

7=STORM 

8=MAX 

9=F&P 

10=W ROBOT 

11=SUN 

12=HUMIDITY 

13=LEE SIDE 

14=WIND 

15=AIR EXCHANGE 

16=OUTLET 

17=RELEASE 

18=SHOWER PROT.P1 

19=SHOWER PROT.P2 

20=EXTRA INFLUENCE 

21=DEV. TEMP 

22=CROP ACT. 

23=INSTALLATION 

24=INCREASE 

25=AIR CIRCULATION 

  

M125 Indication of the limitation of the minimum vent position on the lee side. See Beperking_raamstand_Connext. 

  

VntsLeeSide.CodeLimitMxLee 

60C0 

VENT.CONTR 

Limitation max vent lee 

0=NONE 

1=MIN 

2=CROP TREATM. 

3=CURTAIN 

4=ON/OFF HEAT 

5=RAIN 

6=FROST 

7=STORM 

8=MAX 

9=F&P 

10=W ROBOT 

11=SUN 

12=HUMIDITY 

13=LEE SIDE 

14=WIND 

15=AIR EXCHANGE 

16=OUTLET 

17=RELEASE 

18=SHOWER PROT.P1 

19=SHOWER PROT.P2 

20=EXTRA INFLUENCE 

21=DEV. TEMP 

22=CROP ACT. 

23=INSTALLATION 

24=INCREASE 

25=AIR CIRCULATION 

  

M125 Indication of the limitation of the maximum vent position on the lee side. See Beperking_raamstand_Connext. 

  

VntsLeeSide.MeasVentLeePos 

3DE 

VENT.CONTR 

Measured vent lee 

M125 The measured vent position on the lee side. 

  

VntsWindSide.CalcMaxVentWind 

60DA 

VENT.CONTR 

Calculated max vent wind 

M125  

  

VntsWindSide.CalcMinVentWind 

418 

VENT.CONTR 

Calculated min vent wind 

M125  

  

VntsWindSide.CalcVentWindPos 

3D6 

VENT.CONTR 

Calculated vent wind 

M125  

  

VntsWindSide.CalcVtTempWind 

3EA 

VENT.CONTR 

Calc ventilation temperature wind 

°C 

M120 As soon as the measured temperature rises above the ventilation temperature calculated here for the wind side, then on the wind side the vents will start to be controlled open. 

  

VntsWindSide.CodeLimitMnWind 

3F1 

VENT.CONTR 

Limitation min vent wind 

0=NONE 

1=MIN 

2=CROP TREATM. 

3=CURTAIN 

4=ON/OFF HEAT 

5=RAIN 

6=FROST 

7=STORM 

8=MAX 

9=F&P 

10=W ROBOT 

11=SUN 

12=HUMIDITY 

13=LEE SIDE 

14=WIND 

15=AIR EXCHANGE 

16=OUTLET 

17=RELEASE 

18=SHOWER PROT.P1 

19=SHOWER PROT.P2 

20=EXTRA INFLUENCE 

21=DEV. TEMP 

22=CROP ACT. 

23=INSTALLATION 

24=INCREASE 

25=AIR CIRCULATION 

  

M125  

  

VntsWindSide.CodeLimitMxWind 

3EF 

VENT.CONTR 

Limitation max vent wind 

0=NONE 

1=MIN 

2=CROP TREATM. 

3=CURTAIN 

4=ON/OFF HEAT 

5=RAIN 

6=FROST 

7=STORM 

8=MAX 

9=F&P 

10=W ROBOT 

11=SUN 

12=HUMIDITY 

13=LEE SIDE 

14=WIND 

15=AIR EXCHANGE 

16=OUTLET 

17=RELEASE 

18=SHOWER PROT.P1 

19=SHOWER PROT.P2 

20=EXTRA INFLUENCE 

21=DEV. TEMP 

22=CROP ACT. 

23=INSTALLATION 

24=INCREASE 

25=AIR CIRCULATION 

  

M125  

  

VntsWindSide.MaxRFallPh1Wind 

413 

VENT.CONTR 

Max vent wind rainfall radar phase 1 

I125.1 Limitation of the vent position on the wind side if the rainfall radar is forecasting a precipitation intensity that is greater than the intensity specified for phase 1. 

  

VntsWindSide.MeasVentWindPos 

60E3 

VENT.CONTR 

Measured vent wind 

M125  

  

ALG_POMP_.POMP_DRAAIT 

56F 

WATER TEMP 

Pump active 

0=NO 

1=YES 

  

M115.2 Indication of whether the circulation pump has been activated. 

  

RVW_BUIS.MAX_BUIS 

632 

WATER TEMP 

calculated maximum water temperature 

°C 

I115 Calculated pipe temperatures. 

I116  

M115 The calculated maximum water temperature after the influence(s). 

  

RVW_BUIS.MIN_BUIS 

633 

WATER TEMP 

calculated minimum water temperature 

°C 

I115 Calculated pipe temperatures. 

I116  

M115 The calculated minimum water temperature after the influence(s). 

  

VERWNET.BER_BUIS_T 

651 

WATER TEMP 

calculated water temperature 

°C 

M100.1 The calculated water temperature. 

M106  

M115 The calculated water temperature. 

  

VERWNET.GEM_BUIS_T 

652 

WATER TEMP 

water temperature 

°C 

M100 The measured pipe temperature 

M106  

M115 The measured pipe temperature 

  

VN_RETOUR.GEM_RET_TEMP 

658 

WATER TEMP 

water temperature return 

°C 

M100 The measured return temperature of the pipe. 

M115 The measured return water temperature. 

  

VNET_STREEF.GESEL_MAX_BUIST 

674 

WATER TEMP 

Set max water temperature 

°C 

M115 The set maximum water temperature of the period that is currently activated. 

  

VNET_STREEF.GESEL_MIN_BUIST 

675 

WATER TEMP 

Set min water temperature 

°C 

M115 The set minimum water temperature of the period that is currently activated. 

  

KASL_REF.ATR_GEM_KAS_TEMP 

6A3 

HEAT CONTR 

heating temperature 

°C 

I100 The measured heating temperature (greenhouse or plant temperature). 

M100 The measured heating temperature (greenhouse or plant temperature). 

  

MODVERW_.GER_AUT_VERM 

6CB 

HEAT CONTR 

Act capacity aut heat system 

kW 

M112 The actual capacity by the autonomous heating systems. 

  

VERWCTL.GER_EXT_VERM 

6E3 

HEAT CONTR 

Total external capacity 

kW 

M112 Total sum of the external capacities which influence the capacity demand of the heating control provided by HID lighting and hot air heaters. 

  

VERWCTL.GEW_KASTEMP 

6E5 

HEAT CONTR 

desired heating temperature 

°C 

M100 The calculated heating temperature. 

M100.1 The calculated heating temperature. 

M106 The calculated heating temperature is the same for the heating controls. 

M110 The calculated heating temperature which takes into account influences, maximum increase and maximum decrease of I110.1 Verwarming/Invloeden and temperature balance control. 

M112 The calculated heating temperature which takes into account influences, maximum increase and maximum decrease of I110.1 Verwarming/Invloeden and temperature balance control. 

  

VERWCTL.GEW_VERM_MODVW 

6E7 

HEAT CONTR 

Des capacity heat total 

kW 

M112 The desired capacity for keeping the greenhouse at the correct temperature or getting it there. 

  

VERWCTL.REFERENTIE 

6F6 

HEAT CONTR 

measured heating temperature 

°C 

M106 The calculated heating temperature is the same for the heating controls. 

  

DKMAN.GEW_DKFUNC 

8D2 

CURT CONTR 

Desired curtain function 

0=NONE 

1=HUMIDITY 

2=SHADING 

3=ENERGY 

4=BLACK OUT 

5=SLAVE 

6=SIDE 

  

M160 Indication of the desired (new) curtain function. 

  

EnergCurGen_Calc.CurTotalCond 

5E48 

CURT CONTR 

Calculated status curtain 

0=CLOSE 

1=OPEN 

  

M162 Indicates the desired curtain position, taking into account all the set conditions. 

  

EnergCurGen_Calc.LimitEnergCurStr 

5E5D 

CURT CONTR 

Limitation energy curtain strategy 

0=NONE 

1=PER. END TIME 

2=FORCED OPEN 

3=FORCED CLOSE 

4=AUTO OPEN 

5=AUTO CLOSE 

6=SHOWER PROT. 

  

M162  

  

ENSTR_STEPS.DkPrBovenDkTlu 

5EF3 

CURT CONTR 

Meas temperature above curtain 

°C 

I162.1  

M162  

  

GapControl.CalcedGapSize 

928 

CURT CONTR 

gap size actual 

I165  

M160 The calculated gap size is the largest of the calculated temperature gaps and the calculated humidity gap. 

  

GapControl.DeltaHumAvg 

931 

CURT CONTR 

measured difference humidity 

g/m³ 

I165  

  

GapControl.DeltaTempAvg 

932 

CURT CONTR 

measured difference temperature 

°C 

I165  

  

RVSTW_SAVE.GEW_DKST 

9B3 

CURT CONTR 

Calculated humidity curtain position 

I164  

  

SCSTW.ScDkStandDemp 

9D3 

CURT CONTR 

Calculated shading curtain position 

I163  

  

SDK_StralRef.StralRefVsGem 

9DB 

CURT CONTR 

Used radiation 

W/m² 

I160.4 The radiation that is used to control the shading curtain in the compartment. 

I160.4 The radiation that is used to control the autonomous shading curtain. 

I163  

  

VDSTW.GEW_DKST 

9DF 

CURT CONTR 

Calculated black out curtain position 

I161  

  

VERD_StralRef.StralRefVsGem 

9F1 

CURT CONTR 

applied radiation black out curtain 

W/m² 

I160.4 The radiation that is used to control the black out curtain in the compartment. 

I160.4 The radiation that is used to control the autonomous black out curtain. 

  

VerdDoekPer.VoorwaardeGeldig 

A18 

CURT CONTR 

Condition valid 

0=NO 

1=YES 

  

I161  

  

vlg_doek.BER_DOEKST 

A1B 

CURT CONTR 

Calculated side-slave curtain position 

I166  

  

vlg_doek.MAX_DOEKST 

A1E 

CURT CONTR 

Max curtain position 

I166 Maximum curtain position when the curtain is controlled shut from the side-slave curtain function. 

  

DKST_VB.BEGR_CODE 

A4F 

CURTAIN 

Curtain position limitation 

0=NONE 

1=VENTS 

2=ELECTR 

3=RELEASE 

4=CLOCK 

5=FIXED 

6=INSTALLATION 

7=LIGHTING 

8=CROP TREATM. 

9=VENTIL 

10=GAP 

12=STORM 

13=EXTERNAL MAX 

14=EXTERNAL MIN 

15=SHOWER PROT.P1 

16=SHOWER PROT.P2 

17=LIGHT EMISSION 

  

I168 Indication of the current curtain position limitation. 

M160 Indication of the current curtain position limitation, see I168 Doek sturing. 

  

DKST_VB.BER_DKST 

67AA 

CURTAIN 

Calculated curtain position 

M160 The calculated curtain position from the Actual curtain function . 

  

DKST_VB.DK_FUNC 

A56 

CURTAIN 

Actual curtain function 

0=NONE 

1=HUMIDITY 

2=SHADING 

3=ENERGY 

4=BLACK OUT 

5=SLAVE 

6=SIDE 

  

I168 The active curtain function that determines the curtain position if necessary in combination with a gap control. 

M160 The curtain function that is valid at this moment. 

  

DKST_VB.DoekStandGer 

A5C 

CURTAIN 

Measured curtain position 

M100 The measured curtain position in the compartment. 

M160 The measured curtain position at curtain position measurement and the current curtain position calculated from the run time. 

  

DKST_VB.GEW_DKST 

A62 

CURTAIN 

Desired curtain position 

M160  

  

PARMe.PARGemMed 

BBB 

PAR SENSOR 

PAR 

umol/s/m² 

M4  

M105 The measured PAR in the compartment. If there are several PAR measurements in the compartment, select which measurement is displayed here in I100.3 Installations/Radiation and compartment. 

  

afd_groeilicht.Ger_niveau 

CDA 

CMP 

Number of active growing light steps 

  

M106 Number of growing light steps switched on (undelayed) 

  

AFD_SOM.BER_AFD_STRAL 

CE1 

CMP 

calculated radiation greenhouse 

W/m² 

M100 The calculated radiation in the compartment. This value is calculated based on the measured radiation outside, the height of the sun, the system and its usage. No account is taken of conditions such as whitewashing or pollution of the greenhouse roof, condensation on the greenhouse roof or aging of the (growing light) installation. 

  

AFD_SOM.BER_ASS_STRAL 

CE3 

CMP 

calculated radiation growing light 

W/m² 

M100 The calculated radiation emitted by the growing light. 

  

AfdRegElekSm.ElecTdCompTot 

CFA 

CMP 

Electr.total 

kWh 

M107 Cumulative electricity consumption from the set time in the 24-hour period of all growing light systems and air treatment systems of this compartment. 

  

AfdRegElekSm.ElecTdCompTotM2 

CF9 

CMP 

Electr per m² 

kWh/m² 

M107 Cumulative electricity consumption from the set time in the 24-hour period of all growing light systems and air treatment systems per m² of this compartment. 

  

AfdRegElekSm.ElecYdCompTot 

CF8 

CMP 

Electr.total 

kWh 

M107  

  

AfdRegElekSm.ElecYdCompTotM2 

CF7 

CMP 

Electr per m² 

kWh/m² 

M107  

  

AfdRegGasSm.GasSmTd_m2 

CFD 

CMP 

Gas per m² 

m³/m² 

M107 The gas consumption of today per m² of the compartment. 

  

AfdRegGasSm.GasSmTd_tot 

CFE 

CMP 

Gas total 

m³ 

M107 The total gas consumption of today of the compartment. 

  

AfdRegGasSm.GasSmYd_m2 

CFB 

CMP 

Gas per m² 

m³/m² 

M107  

  

AfdRegGasSm.GasSmYd_tot 

CFC 

CMP 

Gas total 

m³ 

M107  

  

DryPhase.CurrentDryPhase 

D22 

CMP 

Active dry phase 

  

M106 Irrigation has taken place and the stated drying phase is active. 

  

DryPhase.IrrigationActive 

D23 

CMP 

Irrigation active 

0=NO 

1=YES 

  

M106 The irrigation is active. 

  

GEM_GEWASTEMP.GEM_GEWAS_RV 

D29 

CMP 

relative humidity 

M100 The calculated relative air humidity at the measured plant temperature. 

  

GEM_GEWASTEMP.GEM_GEWAS_TEMP 

D2A 

CMP 

Measured plant temperature 

°C 

M100  

  

GEM_GEWASTEMP.GEM_GEWAS_VD 

D2B 

CMP 

humidity deficit 

g/m³ 

M100 The calculated humidity deficit for the measured plant temperature. 

  

GEM_GEWASTEMP.GEM_GEWAS_VPD 

D2C 

CMP 

VPD 

kPa 

M100 The calculated vapour pressure deficit for the measured plant temperature. The vapour pressure deficit is the difference between the vapour pressure in the crop's stomata and the vapour pressure in the greenhouse air. 

  

INVL_FAC_VERW.GESEL_VWTEMP 

D40 

CMP 

Corrected heating temperature 

°C 

M110 The heating temperature, corrected if applicable by the 24h temperature control. This temperature may also be a correction setting. 

  

INVL_FAC_VERW.STW_VERW 

D4E 

CMP 

Calc heating temperature 

°C 

I110 Calculated heating temperature after influence(s). 

I111  

M110 The calculated heating temperature which takes into account influences, maximum increase and maximum decrease in I110.1 Heating/Influences. 

  

KASL_REF.ATR_GEM_KAS_AV 

D58 

CMP 

absolute humidity 

g/m³ 

M100 The measured absolute air humidity. 

  

KASL_REF.ATR_GEM_KAS_CO2 

D59 

CMP 

CO₂ 

ppm 

M100  

  

KASL_REF.ATR_GEM_KAS_RV 

D5A 

CMP 

relative humidity 

M100 The measured relative air humidity. 

  

KASL_REF.ATR_GEM_KAS_TEMP 

D5B 

CMP 

greenhouse temperature 

°C 

M100 The measured greenhouse air temperature. 

  

KASL_REF.ATR_GEM_KAS_VD 

D5C 

CMP 

humidity deficit 

g/m³ 

M100 The measured humidity deficit. 

  

LuchtConditie.ActieveFase 

D88 

CMP 

active phase crop treatment 

0=OFF 

1=PHASE 1 

2=PHASE 2 

3=PHASE 3 

4=PHASE 4 

5=PHASE 5 

6=PHASE 6 

  

M106 The active phase of the crop treatment strategy. 

  

PAR_Ref.PARRefVsGem 

D8E 

CMP 

Measured 

umol/s/m² 

I100 The measured PAR level in the compartment. 

M100 The measured PAR in the compartment. If there are several PAR measurements in the compartment, select which measurement is displayed here in I100.3 Installations/Radiation and compartment. 

  

Temp24hour.Actual24hTemp 

E19 

CMP 

Actual 24 hours temperature current 24 hours 

°C 

I104  

  

Temp24hour.ActualCorrPerc 

E1A 

CMP 

calculated correction 

I104  

  

Temp24hour.ActualRTRvalPAR 

7D86 

CMP 

Actual RTR per 10 mol/m² current 24 hours 

°C 

I104  

  

Temp24hour.ActualRTRvalRad 

7D87 

CMP 

Actual RTR per 1000 J/cm² current 24 hours 

°C 

I104  

  

Temp24hour.DeviationState 

E23 

CMP 

calculated control action 

0=NONE 

1=DECREASE 

2=INCREASE 

  

I104  

  

Temp24hour.Exp24hTActual 

E25 

CMP 

Expected 24 hours temperature until now 

°C 

I104  

  

Temp24hour.Final24hTemp 

E27 

CMP 

Desired 24 hours temperature current 24 hours 

°C 

I104  

I104  

I104  

  

Temp24hour.PrevActual24hT 

E30 

CMP 

Actual 24 hours temperature previous 24 hours 

°C 

I104  

  

Temp24hour.PrevBase24hTemp 

7DB5 

CMP 

Set base temperature previous 24 hours 

°C 

  

Temp24hour.PrevFinal24hT 

E31 

CMP 

Desired 24 hours temperature previous 24 hours 

°C 

I104  

  

Temp24hour.PrevPARSmOutside 

7DB7 

CMP 

Actual RTR PAR sum outside previous 24 hours 

mol/m² 

  

Temp24hour.PrevPARSumInside 

7DB8 

CMP 

Actual RTR PAR sum inside previous 24 hours 

mol/m² 

  

Temp24hour.PrevRadSmOutside 

7DB9 

CMP 

Actual RTR radiation sum outside previous 24 hours 

J/cm² 

  

Temp24hour.PrevRadSumInside 

7DBA 

CMP 

Actual RTR radiation sum inside previous 24 hours 

J/cm² 

  

Temp24hour.PrevRTRvaluePAR 

7D8A 

CMP 

Actual RTR per 10 mol/m² previous 24 hours 

°C 

I104  

  

Temp24hour.PrevRTRvalueRad 

7D8B 

CMP 

Actual RTR per 1000 J/cm² previous 24 hours 

°C 

I104  

  

Temp24hour.PrevSetRTRperKJ 

7DBB 

CMP 

Set RTR per 1000 J/cm² previous 24 hours 

°C 

  

Temp24hour.PrevSetRTRperMol 

7DBC 

CMP 

Set RTR per 10 mol/m² previous 24 hours 

°C 

  

TempStrategy.RecipeHeatTemp 

E40 

CMP 

Set heating temperature 

°C 

M110 The set heating temperature of the period that is currently activated. 

  

TempStrategy.RecipeVentTemp 

E3F 

CMP 

Set ventilation temperature 

°C 

M120 The set ventilation temperature of the period that is currently activated. 

  

TrAfdPARSomRef.PARRefSomBer 

E44 

CMP 

PAR sum 

mol/m² 

M100 The measured PAR sum in the compartment counted from the moment of sunrise (M4 Overzicht/Metingen). 

  

UI_KOEL.BER_KOEL_TEMP 

E49 

CMP 

cooling temperature calculated 

°C 

I220 Calculated temperature of the cold store, greenhouse or greenhouse soil. 

M106  

  

UI_KOEL.BER_VRIJG 

E4A 

CMP 

Release cooling 

0=NO 

1=YES 

  

I220 Indication of whether the cooling has been released. 

  

VENTSTREEF.GES_STW_RAAM 

E73 

CMP 

Corrected ventilation temperature 

°C 

M120 The ventilation temperature, corrected if applicable by the 24h temperature control. This temperature may also be a correction setting. 

  

ZonHoogte.StrDoorlaatAlg 

E96 

CMP 

translucency greenhouse roof 

I101 The translucency used from the greenhouse roof. The translucency is used for several controls, such as the light control, the heating control, the ventilation control, the transpiration sum start in the irrigation and for the calculation of the top temperature of the crop. 

  

Afname_Trafo.ActualCapacity 

6A30 

OFF-TAKE TRA 

Act. electrical capacity 

kW 

M200 The sum of the total maximum electrical capacity of all the growing light systems and other electrical consumers connected to this off-take transformer. 

  

Afname_Trafo.CalcLimitation 

6A31 

OFF-TAKE TRA 

Limitation 

0=NONE 

1=BLOCK 

2=DEMAND MAX 

3=INSTAL MAX 

  

M200 The limitation of the desired electrical capacity of this off-take transformer. 

  

Afname_Trafo.DesiredCapacity 

6A32 

OFF-TAKE TRA 

Des electrical capacity 

kW 

M200 The sum of the total desired capacity that must be supplied to all the connected consumers. 

  

Afname_Trafo.Meas_Sper 

6A37 

OFF-TAKE TRA 

Used value 

0=NO 

1=YES 

  

M200  

  

DKMAN.GEW_DKFUNC 

1094 

CURT CONTR 

Desired curtain function 

0=NONE 

1=HUMIDITY 

2=SHADING 

3=ENERGY 

4=BLACK OUT 

5=SLAVE 

6=SIDE 

  

M160 Indication of the desired (new) curtain function. 

  

EnergCurGen_Calc.CurTotalCond 

5E59 

CURT CONTR 

Calculated status curtain 

0=CLOSE 

1=OPEN 

  

M162 Indicates the desired curtain position, taking into account all the set conditions. 

  

EnergCurGen_Calc.LimitEnergCurStr 

5E72 

CURT CONTR 

Limitation energy curtain strategy 

0=NONE 

1=PER. END TIME 

2=FORCED OPEN 

3=FORCED CLOSE 

4=AUTO OPEN 

5=AUTO CLOSE 

6=SHOWER PROT. 

  

M162  

  

ENSTR_STEPS.DkPrBovenDkTlu 

5F16 

CURT CONTR 

Meas temperature above curtain 

°C 

I162.1  

M162  

  

GapControl.CalcedGapSize 

10EA 

CURT CONTR 

gap size actual 

I165  

M160 The calculated gap size is the largest of the calculated temperature gaps and the calculated humidity gap. 

  

GapControl.DeltaHumAvg 

10F3 

CURT CONTR 

measured difference humidity 

g/m³ 

I165  

  

GapControl.DeltaTempAvg 

10F4 

CURT CONTR 

measured difference temperature 

°C 

I165  

  

RVSTW_SAVE.GEW_DKST 

1175 

CURT CONTR 

Calculated humidity curtain position 

I164  

  

SCSTW.ScDkStandDemp 

1195 

CURT CONTR 

Calculated shading curtain position 

I163  

  

SDK_StralRef.StralRefVsGem 

119D 

CURT CONTR 

Used radiation 

W/m² 

I160.4 The radiation that is used to control the shading curtain in the compartment. 

I160.4 The radiation that is used to control the autonomous shading curtain. 

I163  

  

VDSTW.GEW_DKST 

11A1 

CURT CONTR 

Calculated black out curtain position 

I161  

  

VERD_StralRef.StralRefVsGem 

11B3 

CURT CONTR 

applied radiation black out curtain 

W/m² 

I160.4 The radiation that is used to control the black out curtain in the compartment. 

I160.4 The radiation that is used to control the autonomous black out curtain. 

  

VerdDoekPer.VoorwaardeGeldig 

11DA 

CURT CONTR 

Condition valid 

0=NO 

1=YES 

  

I161  

  

vlg_doek.BER_DOEKST 

11DD 

CURT CONTR 

Calculated side-slave curtain position 

I166  

  

vlg_doek.MAX_DOEKST 

11E0 

CURT CONTR 

Max curtain position 

I166 Maximum curtain position when the curtain is controlled shut from the side-slave curtain function. 

  

DKST_VB.BEGR_CODE 

1211 

CURTAIN 

Curtain position limitation 

0=NONE 

1=VENTS 

2=ELECTR 

3=RELEASE 

4=CLOCK 

5=FIXED 

6=INSTALLATION 

7=LIGHTING 

8=CROP TREATM. 

9=VENTIL 

10=GAP 

12=STORM 

13=EXTERNAL MAX 

14=EXTERNAL MIN 

15=SHOWER PROT.P1 

16=SHOWER PROT.P2 

17=LIGHT EMISSION 

  

I168 Indication of the current curtain position limitation. 

M160 Indication of the current curtain position limitation, see I168 Doek sturing. 

  

DKST_VB.BER_DKST 

67AB 

CURTAIN 

Calculated curtain position 

M160 The calculated curtain position from the Actual curtain function . 

  

DKST_VB.DK_FUNC 

1218 

CURTAIN 

Actual curtain function 

0=NONE 

1=HUMIDITY 

2=SHADING 

3=ENERGY 

4=BLACK OUT 

5=SLAVE 

6=SIDE 

  

I168 The active curtain function that determines the curtain position if necessary in combination with a gap control. 

M160 The curtain function that is valid at this moment. 

  

DKST_VB.DoekStandGer 

121E 

CURTAIN 

Measured curtain position 

M100 The measured curtain position in the compartment. 

M160 The measured curtain position at curtain position measurement and the current curtain position calculated from the run time. 

  

DKST_VB.GEW_DKST 

1224 

CURTAIN 

Desired curtain position 

M160  

  

REG_PEF.BER_VENT_CAP 

14EB 

AUT F&P 

Calculated fan capacity 

  

REG_PEF.REFERENTIE 

14FA 

AUT F&P 

  

°C 

M106  

  

REG_PEF.START_PEF 

14FB 

AUT F&P 

Temperature F&P cooling active 

°C 

  

KASL_REF.ATR_GEM_KAS_TEMP 

1669 

AUT VENT 

ventilation temperature 

°C 

  

TempStrategy.RecipeVentTemp 

1781 

AUT VENT 

Set ventilation temperature 

°C 

M120 The set ventilation temperature of the period that is currently activated. 

  

VENTAFST.STW_RAAM 

17A6 

AUT VENT 

Calc ventilation temperature 

°C 

  

VENTSTREEF.GES_STW_RAAM 

17B8 

AUT VENT 

Corrected ventilation temperature 

°C 

M120 The ventilation temperature, corrected if applicable by the 24h temperature control. This temperature may also be a correction setting. 

  

VntsControl.MeasCtrlTemp 

17AA 

AUT VENT 

  

°C 

M106  

  

VntsLeeSide.CalcMaxVentLee 

60BB 

AUT VENT 

Calculated max vent lee 

M125 The calculated maximum vent position for the lee side after possible limitations. 

  

VntsLeeSide.CalcMinVentLee 

1703 

AUT VENT 

Calculated min vent lee 

M125 The calculated minimum vent position on the lee side. 

  

VntsLeeSide.CalcVentLeePos 

16C0 

AUT VENT 

Calculated vent lee 

M125 The calculated vent position on the lee side. 

  

VntsLeeSide.CalcVtTempLee 

60BC 

AUT VENT 

Calc ventilation temperature lee 

°C 

M120 As soon as the measured temperature rises above the ventilation temperature calculated here for the lee side, then on the lee side the vents will start to be controlled open. 

  

VntsLeeSide.MeasVentLeePos 

16CA 

AUT VENT 

Measured vent lee 

M125 The measured vent position on the lee side. 

  

VntsWindSide.CalcMaxVentWind 

60DB 

AUT VENT 

Calculated max vent wind 

M125  

  

VntsWindSide.CalcMinVentWind 

1704 

AUT VENT 

Calculated min vent wind 

M125  

  

VntsWindSide.CalcVentWindPos 

16C2 

AUT VENT 

Calculated vent wind 

M125  

  

VntsWindSide.CalcVtTempWind 

16D6 

AUT VENT 

Calc ventilation temperature wind 

°C 

M120 As soon as the measured temperature rises above the ventilation temperature calculated here for the wind side, then on the wind side the vents will start to be controlled open. 

  

VntsWindSide.MeasVentWindPos 

60E2 

AUT VENT 

Measured vent wind 

M125  

  

ALG_POMP_.POMP_DRAAIT 

1A14 

AUT HEAT 

Pump active 

0=NO 

1=YES 

  

  

INVL_FAC_VERW.GESEL_VWTEMP 

1A5B 

AUT HEAT 

Corrected heating temperature 

°C 

M110 The heating temperature, corrected if applicable by the 24h temperature control. This temperature may also be a correction setting. 

  

INVL_FAC_VERW.STW_VERW 

1A69 

AUT HEAT 

Calc heating temperature 

°C 

  

KASL_REF.ATR_GEM_KAS_TEMP 

1A72 

AUT HEAT 

heating temperature 

°C 

  

RVW_BUIS.MAX_BUIS 

1B3A 

AUT HEAT 

calculated maximum water temperature 

°C 

  

RVW_BUIS.MIN_BUIS 

1B3B 

AUT HEAT 

calculated minimum water temperature 

°C 

  

TempStrategy.RecipeHeatTemp 

1B63 

AUT HEAT 

Set heating temperature 

°C 

M110 The set heating temperature of the period that is currently activated. 

  

VERWCTL.GER_EXT_VERM 

1B8C 

AUT HEAT 

Total external capacity 

kW 

M112 Total sum of the external capacities which influence the capacity demand of the heating control provided by HID lighting and hot air heaters. 

  

VERWCTL.GER_VERM 

1B8D 

AUT HEAT 

Act capacity heat system 

kW 

M112 The actual capacity by the heating system. 

  

VERWCTL.GEW_KASTEMP 

1B8E 

AUT HEAT 

desired heating temperature 

°C 

  

VERWCTL.GEW_VERM_MODVW 

1B90 

AUT HEAT 

Des capacity heat total 

kW 

M112 The desired capacity for keeping the greenhouse at the correct temperature or getting it there. 

  

VERWCTL.REFERENTIE 

1B9F 

AUT HEAT 

  

°C 

M106 The calculated heating temperature is the same for the heating controls. 

  

VERWNET.BER_BUIS_T 

1BAC 

AUT HEAT 

calculated water temperature 

°C 

  

VERWNET.GEM_BUIS_T 

1BAE 

AUT HEAT 

Meas water temperature 

°C 

  

VNET_STREEF.GESEL_MAX_BUIST 

1BD1 

AUT HEAT 

Set max water temperature 

°C 

M115 The set maximum water temperature of the period that is currently activated. 

  

VNET_STREEF.GESEL_MIN_BUIST 

1BD2 

AUT HEAT 

Set min water temperature 

°C 

M115 The set minimum water temperature of the period that is currently activated. 

  

KASLBOX.GEM_CO2 

1D72 

AUT REF 

CO₂ 

ppm 

  

KASLBOX.GEM_KAS_RV 

1D73 

AUT REF 

relative humidity 

  

KASLBOX.GEM_KAS_VD 

1D74 

AUT REF 

humidity deficit 

g/m³ 

  

KASLBOX.GEM_KASNBOL 

1D75 

AUT REF 

WBT 

°C 

  

KASLBOX.GEM_KASTEMP 

1D76 

AUT REF 

temperature 

°C 

  

PAR_Ref.PARRefVsGem 

21AD 

GR. PROGR 

applied PAR 

umol/s/m² 

I205  

I205.4 The used PAR for the growing light program. 

  

Stral_Ref.StralRefVsGem 

21B2 

GR. PROGR 

Used radiation 

W/m² 

I205  

I205.4 The used radiation for the growing light program. 

  

STW_ASSB.CdBelAan 

21B7 

GR. PROGR 

Switch on desire 

0=NONE 

1=LIGHTING 

2=EXTERNAL 

  

I205 Indication of the desire to switch on the growing light. 

  

STW_ASSB.CdBep 

21B8 

GR. PROGR 

Limitation 

0=NONE 

1=MEAS RAD. SUM 

2=MEAS PAR SUM 

3=EXP RAD. SUM 

4=EXP PAR SUM 

5=LONG DAY 

6=EXTERN OFF 

7=ADJUST LIMIT 

8=REL.OUTSIDE TEMP 

9=EXTERN ON 

  

I205  

  

STW_ASSB.GER_STRAL_SOM 

21BB 

GR. PROGR 

radiation sum today 

J/cm² 

I205  

  

STW_ASSB_PAR.AbPrPARGerSomVd 

21C3 

GR. PROGR 

PAR sum today 

mol/m² 

I205  

  

VERW_PAR_SOM.HuidigEtmaal 

21C7 

GR. PROGR 

expected PAR sum today 

mol/m² 

I205  

  

KDAS_STU.BER_BEPERKING 

21D0 

STRING 

Limitation 

0=NONE 

1=RADSUM 

2=MIN T ON 

3=MIN T OFF 

4=WAIT REL 

5=END TIME 

6=WAIT HEAT ON 

7=WAIT HEAT OFF 

8=CROP TREATM. 

9=WAIT CURTAIN 

10=REL.OUTSIDE TEMP 

11=FIXED POS, OFF 

12=FIXED POS, ON 

13=EXTERN OFF 

14=EXTERN ON 

15=DEALER DRIVE 

16=INSTALLATION 

17=PERIOD SWITCH OFF 

18=LOCAL BLOCK 

19=ALWAYS FORCED OFF 

  

I206 The limitation for the string of the growing light system. 

M205 See I206 Groeilicht systeem/Realisatie. 

  

KDAS_STU.TOEST_UITG 

21DC 

STRING 

Act status string 

0=OFF 

1=ON 

  

I206 Actual status of the string. 

M205 The actual status of string X of the growing light system. 

  

AB_SYS.GER_AB_TOEST 

21E8 

SW. LIGHT 

Actual status 

0=OFF 

1=MIN T OFF 

2=WAIT REL 

3=ON 

4=MIN T ON 

5=WAIT ON 

6=WAIT OFF 

  

I206  

  

AB_SYS.gew_ab_toest 

21EA 

SW. LIGHT 

  

0=OFF 

1=ON 

  

  

KRAANGRP.DOORLOOP 

2234 

VALVE GRP 

Number of times phase active 

  

I401 Indication of the number of times (see 17 Number of times phase ) that the phase has been run. This can be used to follow the progress of the irrigation. 

  

KRAANGRP.HWATER_STRALSOM 

223E 

VALVE GRP 

highest quantity water per radiation sum 

ml/MJ 

M100 The highest water dosage of the valve group. 

M430 The highest water dosage of the valve group. Deviations are reported, see Meldingen en alarmen. 

  

KRAANGRP.LWATER_STRALSOM 

2244 

VALVE GRP 

lowest quantity water per radiation sum 

ml/MJ 

M100 The lowest water dosage of the valve group. The Water per rad.sum is the quantity of water per radiation sum, determined over the last 3 irrigation cycles. 

M430 The lowest water dosage of the valve group. The quantity of water per radiation sum, determined over the last 3 irrigation cycles. Deviations are reported, see Meldingen en alarmen. 

  

KRAANGRP.TOESTAND 

2253 

VALVE GRP 

Status valve group 

0=REST 

1=WAITING 

2=PHASE 1 

3=PHASE 2 

4=PHASE 3 

5=PHASE 4 

6=PHASE 5 

7=WAIT 

8=EXT WAIT 

9=PHASE WAIT 

10=ABORT 

11=ERROR 1 

12=ERROR 2 

13=ERROR 3 

14=ERROR 4 

15=ERROR 5 

  

I401 Status indication of the valve group. 

I402 Status indication of the valve group. 

M100 See Status in I402 Handstart/Kraangroep & start. 

M430 See Status in I402 Handstart/Kraangroep & start. 

  

NET_ELB.BEPERKING 

2262 

ELECTR.NETW 

Limitation 

0=NONE 

1=BLOCK 

  

M200 The limitation of the electricity network. 

  

NET_ELB.BRON_PRODUCEERT 

2263 

ELECTR.NETW 

Electricity production active 

0=NO 

1=YES 

  

M200 Indication whether the electricity production by the network is active. 

  

NET_ELB.GemVeExpMom 

2267 

ELECTR.NETW 

Measured electrical export 

kW 

M200 Measured quantity of electricity that is supplied to the electricity network. 

  

NET_ELB.GemVeImpMom 

2268 

ELECTR.NETW 

Measured electrical import 

kW 

M200 Measured quantity of electricity that the electricity network supplies. 

  

NET_ELB.GER_CAP_BRON 

2269 

ELECTR.NETW 

Max electrical capacity 

kW 

M200 The maximum electrical capacity to be supplied by the electricity network. 

  

NET_ELB.GEW_VERM_BRON 

226A 

ELECTR.NETW 

Des electrical capacity 

kW 

M200 The electrical capacity demanded from the electricity network. 

  

MENGER.BEPERKING 

2307 

MIXER 

Limitation 

0=NONE 

1=CHANNEL 

2=NO TANK 

3=CONFIGURATION 

4=STEP 

5=POWER FAILURE 

6=EXT ERROR 

7=PUMP ERROR 

8=FLOW TOO LOW 

9=FLOW TOO HIGH 

10=LEAKAGE ! 

11=MONITOR WATER VALVE 

12=OPEN WATER VALVE 

13=MONITOR FERTILIZER 

14=OPEN FERTILIZER 

15=TANK 0 LITER 

20=SELECT TANK 

21=FRESH WATER 

30=FLOW DEFECTIVE 

31=ALARM SELECT TANK 

32=ALARM PUMP TANK 

33=LEVEL TOO HIGH TANK 

41=ALARM SEL INT TANK 

42=AL PUMP INTERM TANK 

43=AL DRAIN INTER TANK 

44=AL RINSE INTER TANK 

45=LEVEL TOO HIGH ITNK 

46=INT TANK NOT EMPTY 

47=ERROR INTERM TANK 

100=I/O WATER VALVE 

101=I/O PUMP 

102=I/O SELECT TANK 

103=I/O SEL INTERM TANK 

104=I/O PUMP TANK 

105=I/O MIX CHANNEL 

106=I/O FLOW 

107=I/O DRAIN INT.TANK 

108=I/O RINSE INT. TANK 

110=START RINSE 

111=MINIMUM RINSE 

112=MAXIMUM RINSE 

113=END RINSE 

  

I428  

I428.1 See I428 Meststof instellingen 

  

MENGER.BUSY_STAP 

2309 

MIXER 

Step 

  

I428.1 The current step in the mixing process, you can find an overview of all steps in line 2. 

  

MENGER.BUSY_TOESTAND 

230A 

MIXER 

Status step 

0=--- 

1=STOP 

11=RINSE ► 

12=RINSE ►► 

13=RINSE ►►► 

20=LEAKAGE ? 

21=MIX ► 

22=MIX ►► 

31=READY 

  

I428.1 The following statuses are passed through during every step. 

  

MENGER.START 

2320 

MIXER 

Fill 

0=NO 

1=ALL TANKS 

2=FERTILIZER-T 

3=A-TANK 

4=B-TANK 

5=C-TANK 

6=D-TANK 

7=LYE-TANK 

8=ACID-TANK 

12=MIN FERTILIZER-T 

13=MIN A-TANK 

14=MIN B-TANK 

15=MIN C-TANK 

16=MIN D-TANK 

17=MIN LYE-TANK 

18=MIN ACID-TANK 

  

I428  

I428.1 See I428 Meststof instellingen 

  

MENGER.TOESTAND 

2324 

MIXER 

status fertilizer mixer 

0=--- 

1=STOP 

2=REST 

10=FILL TANK 

11=FILL INTERMED TANK 

20=INTERM TANK -> TANK 

21=INTERM TANK ->DRAIN 

30=ERROR 

40=WAIT 

  

I428  

I428.1 See I428 Meststof instellingen 

  

UniMeasurements.ValueUni 

7AA6 

CUSTOM MEAS 

Uni 

  

I705 The result of universal measurement, without unit. 

  

CoBh_DosRef.DosFcoGew 

2671 

CO₂ MANAGEM 

Des CO₂ production 

kg CO₂/hr 

M250  

M250.1 Desired CO2 production for the CO2 management. This demand is determined by adding the CO2 demands from the CO2 controls. 

M250.2 The desired CO2 production for the CO2 management. This demand is determined by adding the CO2 demands from the CO2 controls. 

  

CoBh_Lev.FcoGer 

2676 

CO₂ MANAGEM 

Act CO₂ production 

kg CO₂/hr 

M250  

M250.1 The actual CO2 production by the CO2 management. 

  

CoBh_Verd.BeperkCdBer 

2686 

CO₂ MANAGEM 

Limitation CO₂ production 

0=NONE 

1=ALTERNATIVE 

2=HEAT BY-PRODUCT 

3=MAX VALVES 

4=MAX SOURCES 

5=NUMBER ON 

6=EMERGENCY STOP 

  

M250  

  

CoBh_Verd.VerdFcoMax 

2693 

CO₂ MANAGEM 

Max CO₂ production 

kg CO₂/hr 

M250  

  

AUS_UI_METEN.CD_AUS_TST_BER 

26D1 

EXTERNAL CO₂ 

Status 

0=OFF 

1=DES ACTIVE 

2=ACTIVE 

3=ERROR 

  

M260 The status of the external CO2 source. 

  

CO2Bron_Prod.CdactBer 

26EB 

EXTERNAL CO₂ 

CO₂ production active 

0=NO 

1=YES 

  

M250  

M255 Indication of whether CO2 is being dosed with this source. 

M260 Indication whether there is CO2 dosage with the external CO2 source. 

  

CO2Bron_Prod.FcoGer 

26EC 

EXTERNAL CO₂ 

CO₂ kg per hour 

kg CO₂/hr 

I260 The actual CO2 production of the external CO2 source. 

M250  

M255 The actual CO2 production by this source. 

M260 The actual CO2 production by the external CO2 source. 

  

CO2Bron_Vrg.FcoGew 

26F1 

EXTERNAL CO₂ 

Des CO₂ production 

kg CO₂/hr 

I260 The CO2 demand that is requested by the CO2 management from the external CO2 source and that must be produced by the external CO2 source. 

M250  

M255 The desired CO2 production for this source. 

M260 The desired CO2 production for external CO2 source, that is demanded from the CO2 management. 

  

PULSM_CO2.FLOW 

273F 

EXTERNAL CO₂ 

Current consumption 

unit/hour 

  

CoRgDosBerCo.AanpDempBer 

2824 

CO₂ DOSAGE 

influence smoothing 

kg CO₂/ha/hr 

I170 Calculated influence of the damping on the desired CO2 dosage/concentration. 

M170  

  

CoRgDosBerCo.ActDosGewBer 

282B 

CO₂ DOSAGE 

calculated dosage 

kg CO₂/ha/hr 

I170 Calculated CO2 dosage depending on the set CO2 dosage and influences. 

I170 Calculated CO2 dosage depending on the set CO2 dosage and influences. 

M170 Calculated CO2 dosage, depending on the set CO2 dosage and influences of wind speed, vent position, temperature, humidity, F&P systems, climate and crop treatment. 

  

CoRgDosBerCo.DosGewBer 

282E 

CO₂ DOSAGE 

set dosage 

kg CO₂/ha/hr 

I170 The set CO2 dosage determined from the radiation-dependent settings of the Radiation : dosage setting table. 

M170 The set CO2 dosage determined from the radiation-dependent settings of the Radiation : dosage setting table (I170 CO2-programma/Strategie). 

  

CoRgDosBerConc.CcoGew 

2837 

CO₂ DOSAGE 

Set CO₂ concentration 

ppm 

I170 The set CO2 concentration determined from the radiation-dependent settings of the Radiation : desired concentration setting table. For the CO2 concentration, the Deviation CO₂ conc : CO₂ dos (I170.1 CO2-programma/Invloeden) setting is also of importance. 

M170 The set CO2 concentration determined from the radiation-dependent settings of the Radiation : desired concentration setting table (I170 CO2-programma/Strategie). 

  

CoRgDosBerConc.CcoGewBer 

2838 

CO₂ DOSAGE 

Calculated CO₂ concentration 

ppm 

I170 The calculated CO2 concentration, depending on the set CO2 dosage and influences of wind speed, vent position, temperature, humidity, F&P systems, climate and after possible blocking by the crop treatment. 

M170 The calculated CO2 concentration, depending on the set CO2 concentration and influences of wind speed, vent position, temperature, humidity, F&P systems, climate and crop treatment. 

  

CoRgDosBerGas.ActDosGewBer 

2842 

CO₂ DOSAGE 

calculated dosage 

m³ gas/ha/hr 

I170 Calculated CO2 dosage depending on the set CO2 dosage and influences. 

M170 Calculated CO2 dosage, depending on the set CO2 dosage and influences of wind speed, vent position, temperature, humidity, F&P systems, climate and crop treatment. 

  

CoRgDosBerGas.DosGewBer 

2845 

CO₂ DOSAGE 

set dosage 

m³ gas/ha/hr 

I170 The set CO2 dosage determined from the radiation-dependent settings of the Radiation : dosage setting table. 

M170 The set CO2 dosage determined from the radiation-dependent settings of the Radiation : dosage setting table (I170 CO2-programma/Strategie). 

  

CoRgMomCo.DosTotaalBer 

2849 

CO₂ DOSAGE 

actual dosage total 

kg CO₂/ha/hr 

M170 Actual total dosage (flow). This is the sum of Actual dosage active , Actual dosage passive and Actual dosage on-off heating (flow). 

  

CoRgMomGas.DosTotaalBer 

284E 

CO₂ DOSAGE 

actual dosage total 

m³ gas/ha/hr 

M170 Actual total dosage (flow). This is the sum of Actual dosage active , Actual dosage passive and Actual dosage on-off heating (flow). 

  

CoRgToest.CdBeperkKlimBew 

2852 

CO₂ DOSAGE 

Climate limitation 

0=NONE 

1=TEMPERATURE 

2=HUMIDITY 

3=CONCENTRATION 

4=MEAS.DEFECTIVE 

5=AIR QUALITY 

6=CROP TREATM. 

7=FAN AIRTREATMENT 

  

I170.1  

M170 Indication of the limitation by the climate. 

  

CoRgToest.ConcGem 

2854 

CO₂ DOSAGE 

Measured CO₂ concentration 

ppm 

I170 The measured CO2 concentration. 

I170.1  

M170 The measured CO2 concentration. 

  

CoRgToest.ConcMaxBer 

2856 

CO₂ DOSAGE 

Calc maximum CO₂ concentration 

ppm 

I170.1  

M170  

  

CoRgToest.DosType 

2858 

CO₂ DOSAGE 

Dosage type 

0=NONE 

1=PASSIVE 

2=ACTIVE 

3=BOTH 

  

M170 Selection of the type of dosage. 

  

FanStat.CdStatBer 

28D6 

FAN 

Status 

0=OFF 

1=ON 

2=MIN TIME OFF 

3=MIN TIME ON 

4=NOT CONTROLLED 

  

I255  

  

CoTr_Toest.DosCcoGem 

28E8 

CO₂ TRANSP 

Measured CO₂ concentration 

ppm 

I255 Display of the highest measured CO2 concentration of all connected CO2 controls at this moment. 

  

PlantRefs.CropActLimitDown 

2C07 

CROP MONITOR 

crop activity lower limit 

I106 The limit below which the influences of the crop monitor control are active. 

  

PlantRefs.CropActLimitUp 

2C08 

CROP MONITOR 

crop activity upper limit 

I106  

  

PlantRefs.CropActSmoothed 

2C0C 

CROP MONITOR 

measured crop activity 

I106  

M100 The measured crop activity expressed in a percentage from 0 to 100%. 

  

PlantRefs.CropPerfPast24h 

2C2E 

CROP MONITOR 

crop performance 24-hours 

  

I106  

  

DischargeProg.DischargeState 

63F5 

DISCH. WATER 

Status 

0=REST 

1=RECIPE 

2=START 

3=OPERATION 

  

I445 The status of the fill valve. 

M430 Status of the discharge program (see I445). 

M440 Status of the discharge program (see I445). 

  

DRAIN_BER.ETM_DRN_PR_CONT 

2CB7 

DRAIN TRAY 

24 hours drain percentage 

I405.1  

  

TENSIO_M.TENSIO 

2CF9 

TENSIOMETER 

Tensio 

hPa 

I405.1 Tension limit that is measured at this moment. 

M405 The average tensio (tension of the ground) per tensio meter after the 24 hour period transition. 

M405 The measured tensio (tension of the ground) per tensio meter. 

  

MoistureMeas.UsedEC 

2CFE 

SUBSTRATE 

used EC 

mS/cm 

I405.1 In the event of multiple measurements, the measurement value used is shown here (average, highest or lowest, depending on the selection in I405.4). 

I405.4 The measured EC value in the substrate, depending on the selection of average, highest or lowest. 

M405 The average EC of the slab after the 24-hour transition which is measured with the substrate meter. 

M405 The measured EC in the substrate, measured with a substrate meter. 

  

MoistureMeas.UsedTemperature 

2CFF 

SUBSTRATE 

used temperature 

°C 

I405.1 In the event of multiple measurements, the measurement value used is shown here (average, highest or lowest, depending on the selection in I405.4). 

I405.4 The measured temperature in the substrate, depending on the selection of average, highest or lowest. 

M405 The measured temperature in the substrate, measured with a substrate meter. 

  

ROOTO_GEM.Indroging 

2D12 

SLAB WEIGHER 

Dry-out 

l/m² 

I405.1 The calculated dry-out of the slab in l/m2. The dry-out is calculated by the transpiration model and a drain quantity measurement such as the Priva Irrigation Measurement. 

M405 The calculated dry-out of the slab in l/m2 indicates how far away the mat is from saturation. The dry-out is calculated using the transpiration model and the weight measurement of the Groscale. 

  

ROOTO_GEM.MeasTranspRate 

7DAC 

SLAB WEIGHER 

Transpiration rate 

l/m²/hr 

I405.1 The speed of transpiration. This speed is calculated using the transpiration model and a drain quantity measurement such as the Priva Irrigation Measurement. 

M405 The speed of the transpiration. This speed is calculated using the transpiration model and the measurement of the Groscale. The difference between the Groscale and the standard weight measurements is the unique interface with the control software. This means minor differences can be measured reliably and from this the transpiration is deducted. 

  

ROOTO_GEM.VerzGewicht 

2D16 

SLAB WEIGHER 

Saturation weight 

kg 

I405.1 The weight of the saturated slab. If there is sufficient drain (more than 5%) after a cycle, the substrate is considered saturated. The weight at that moment is the saturation weight. It gives an indication of the condition of the substrate. 

M405 The weight of the saturated slab. If there is sufficient drain (more than 5%) after a cycle, the substrate is considered saturated. The weight at that moment is the saturation weight. It gives an indication of the condition of the substrate. 

  

VOCHT_GEM.GEWICHT 

2D1B 

SLAB WEIGHER 

Weight 

kg 

I405.1 The measured weight of the slab. 

M405 The measured weight of the slab. 

  

DRN_GEG.BEURT_DR_GEM_EC 

2D2B 

MOIST MEAS 

EC 

mS/cm 

M405 The EC drain of the last irrigation cycle. 

  

DRN_GEG.BEURT_DR_GEM_PH 

2D2C 

MOIST MEAS 

pH 

pH 

M405 The pH drain of the last irrigation cycle. 

  

DRN_GEG.BEURT_DRN_CONT 

2D2D 

MOIST MEAS 

Drain 

M405 The measured drain quantity of a cycle. This quantity keeps on rising until the time of the next start. At the end of a cycle, after the draining period, a drain is calculated in l/m2 and a drain percentage determined from this drain quantity and the measured water dose through the water system. After a start, the quantity begins again at 0 litres. 

  

DRN_GEG.BEURT_DRN_OPP 

2D2E 

MOIST MEAS 

Drain 

l/m² 

M405 The drain in litres per m2 of greenhouse area of the last irrigation cycle. 

  

DRN_GEG.BEURT_DRN_PR 

2D2F 

MOIST MEAS 

cycle drain % 

M405 The average drain percentage of the last irrigation cycle. 

  

DRN_GEG.BEURT_OPN_OPP 

2D30 

MOIST MEAS 

Take up 

l/m² 

M405 The quantity of water absorbed by the plant after the last irrigation cycle. This is calculated by subtracting the measured drain quantity from the given quantity. If a drain quantity measurement such as the Precision Irrigation Management is present, an abrupt increase or decrease in weight can also be taken into account. 

  

DRN_GEG.BEURT_TOESTAND 

2D31 

MOIST MEAS 

Status cycle drain 

0=REST 

1=CHECK 

2=OPERATION 

3=START 

4=RESTART 

5=IRR CYCLE 

6=WAIT FOR DRAIN END 

7=MEASURE 

  

M405  

  

DRN_GEG.ETM_DRN_OPP_C 

2D36 

MOIST MEAS 

Drain 

l/m² 

M405 The drain in litres per m2 greenhouse area after the 24 hour period transition. 

  

DRN_GEG.ETM_DRN_PR_CONT 

2D38 

MOIST MEAS 

cycle drain % 

M405 The average drain percentage after the 24 hour period transition. 

  

DRN_GEG.ETM_OPN_OPP_C 

2D3B 

MOIST MEAS 

Take up 

l/m² 

M405 The quantity of water absorbed by the plant after the 24-hour transition. This is calculated by subtracting the measured drain quantity from the given quantity. If a drain quantity measurement such as the Precision Irrigation Management is present, an abrupt increase or decrease in weight can also be taken into account. 

  

GIFT_GEG.BEURT_GIFT_OPP 

2D48 

MOIST MEAS 

Dose 

l/m² 

M405 The water dose in litres per m2 of greenhouse area of the last irrigation cycle. 

  

GIFT_GEG.ETM_GIFT_OPP_C 

2D4C 

MOIST MEAS 

Dose 

l/m² 

M405 The water dose in litres per m2 greenhouse area after the 24 hour period transition. 

  

VOCHT_BEW.VOCHTGEHALTE_A 

2D7F 

MOIST MEAS 

moisture level 

I405 The moisture level that is being monitored. This value is set in the linked start strategy. The measured moisture level is determined by means of the slab weight or a moisture level measurement. 

M405 The measured moisture level of the substrate, measured with a slab weigher or with a substrate meter. 

  

EBMeasure.ActElecOffTake 

7CE1 

E-boiler 

Actual electricity off-take 

kW 

M315 The current electricity consumption of the e-boiler. 

  

EBMeasure.ActHeatCap 

7CE2 

E-boiler 

Actual heat production 

kW 

M300  

M315 The heat capacity currently produced by the e-boiler. 

  

EBMeasure.ActReturnTemp 

7CE9 

E-boiler 

Measured return temperature 

°C 

M300.1 The measured return temperature. 

M315 The measured return temperature. 

  

EBMeasure.ActSupplyTemp 

7CEA 

E-boiler 

Measured supply temperature 

°C 

M300.1 The measured supply temperature. 

M315 The measured supply temperature. 

  

EBMeasure.ControlStatus 

7CF4 

E-boiler 

Status e-boiler control 

0=NOT OPERABLE 

1=OFF 

2=ON 

3=PRE-RUNNING 

4=SHUTTING DOWN 

5=COOLING DOWN 

  

M300.1 See 8 Status e-boiler control . 

M315  

  

EBMeasure.DesElectricCap 

7CF6 

E-boiler 

Des adjustment electrical capacity 

kW 

M315 The desired adjustment of the capacity by the electricity management. 

  

EBMeasure.DesExternalCap 

7CF8 

E-boiler 

Des external electrical capacity 

kW 

M315 The desired electrical capacity, based on External capacity . 

  

EBMeasure.DesReserveCap 

7CFA 

E-boiler 

Des reserve capacity 

kW 

M300  

M315 The desired reserve capacity, based on heat management (I300). 

  

EBMeasure.DesStorageCap 

7CFB 

E-boiler 

Des forced storage capacity 

kW 

I315.2 Desired capacity of the e-boiler that is calculated for the filling of the heat buffer in the active period. 

M300  

M315 The desired forced storage capacity, as set in I315.2 E-boiler gedwongen opslag. 

  

EBMeasure.SystemLimitation 

7D0E 

E-boiler 

Limitation 

0=NONE 

1=CONFIGURATION ERROR 

2=INSTALLATION 

3=LOCAL BLOCK 

4=EMERGENCY HOLD 

5=FAILURE 

6=PRESSURE 

7=NO FLOW 

8=NOT ACTIVE 

9=TEMP. TOO HIGH 

10=WAIT REL 

11=COOLING WATER 

12=BUFFER 

13=TEMP. TOO LOW 

  

M300.1 See 9 Limitation . 

M315  

  

EL_BEH.GEINV_VERM 

2E4D 

ELECTR.MAN 

Total desired electrical capacity 

kW 

M200 The total desired electrical capacity by all electricity consumers, whereby the switching times, delays and maximum available electrical capacity are not taken into account. 

  

EL_BEH.GER_VERM_UI 

2E4F 

ELECTR.MAN 

total limited desired electrical capacity 

kW 

M200 The total desired electrical capacity by all electricity consumers, which is limited by the maximum available electrical capacity. The switching times and delays are taken into account. 

  

EL_BEH.MAX_EL_VERM 

2E50 

ELECTR.MAN 

Max electrical capacity 

kW 

M200 The maximum available electrical capacity. 

  

ElekMomRegis.BerVeBeschikMom 

2E8E 

ELECTR.MAN 

Total measured electrical capacity 

kW 

M200 The measured total electrical capacity. 

  

ElekMomRegis.GemVeExpMom 

2E97 

ELECTR.MAN 

Measured electrical export 

kW 

M204 The measured electricity export. 

  

ElekMomRegis.GemVeImpMom 

2E98 

ELECTR.MAN 

Measured electrical import 

kW 

M204 The measured electricity import. 

  

ElekMomRegis.GemVeProdMom 

2E99 

ELECTR.MAN 

measured electricity production CHP 

kW 

M204 The measured electricity production by the CHP(s). 

  

GASBEGRENS.BER_CORR_GASM 

3031 

GAS DISTR 

Calc max gas consumption 

m³/hr 

I304 The calculated maximum gas consumption of the (external) gas strategy or external gas maximum. 

M304 The calculated maximum gas consumption at this applies at this moment. The maximum gas consumption can be the absolute maximum gas consumption, the maximum from the gas strategy, from the external gas strategy or a contact maximum gas consumption. This calculated maximum gas consumption is including the decrease by controlled and uncontrolled gas consumers. 

M304.1  

  

GASBEGRENS.GASMETING 

303B 

GAS DISTR 

Measured gas consumption 

m³/hr 

I304 The measured gas consumption by a connected pulse meter. 

  

GASBEGRENS.MOM_GASVERBR 

3044 

GAS DISTR 

Calc gas consumption 

m³/hr 

I304 The calculated gas consumption based on the actual capacity and the efficiency of the active heat sources. 

M304.1  

  

GEMID_GASVERBR.GER_GASSOM 

3066 

GAS DISTR 

Measured gas sum 

m³ 

M304 The cumulated measured gas consumption in the period for the average gas consumption. 

  

GEMID_GASVERBR.MAX_GASSOM 

306A 

GAS DISTR 

Maximum gas sum 

m³ 

M304 The cumulated maximum gas consumption in the period for the average gas consumption. This maximum gas sum depends on the length of the period and the specified (absolute) maximum gas consumption. 

  

AirTreatment.CalcSupplyHumRat 

6D62 

ATU 

Calculated supply air AH ratio 

g/kg 

M195 The calculated absolute air humidity ratio. 

  

AirTreatment.CalcSupplyTemp 

6D64 

ATU 

Calculated supply air temperature 

°C 

M195 The calculated temperature of the air that is blown into the indoor area. 

  

AirTreatment.CoolAirHum 

6D66 

ATU 

Cooling air humidity 

M195 The humidity measurement on the outlet side of the cold block. 

  

AirTreatment.CoolAirTemp 

6D68 

ATU 

Cooling air temperature 

°C 

M195 The temperature measurement on the outlet side of the cold block. 

  

AirTreatment.Fan 

6D69 

ATU 

Fan 

0=NO 

1=YES 

  

M195 The supply fan is active. 

  

AirTreatment.FanCapacity 

6D6C 

ATU 

Fan capacity 

M195 The capacity of the supply fan. 

  

AirTreatment.FanDefect 

6D6E 

ATU 

Fan failure 

0=NO 

1=YES 

  

M195.1 Failure message of the fan. 

  

AirTreatment.FanIntervention 

6D71 

ATU 

Fan intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

AirTreatment.MeasSupplyHumRat 

6D73 

ATU 

Measured supply air AH ratio 

g/kg 

M195 The measured absolute air humidity ratio. 

  

AirTreatment.MeasSupplyHumRel 

6D74 

ATU 

Measured supply air RH 

M195 The measured air humidity 

  

AirTreatment.MeasSupplyTemp 

6D76 

ATU 

Measured supply air temperature 

°C 

M195 The measured temperature of the supply air. 

  

AirTreatment.MixHumCool 

6D78 

ATU 

Mixed air humidity 

M195 The air humidity of the mixed air. 

  

AirTreatment.MixTempCool 

6D7A 

ATU 

Mixed air temperature 

°C 

M195 The temperature of the mixed air. 

  

AirTreatment.OuterValve 

6D7C 

ATU 

Outside damper position 

M195 The valve position of the outside air section. 

  

AirTreatment.OuterValveDefect 

6D7F 

ATU 

Outside damper error 

0=NO 

1=YES 

  

M195.1 A error message has been detected. 

  

AirTreatment.OuterValveInter 

6D81 

ATU 

Outside damper intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

AirTreatment.PumpCool 

6D83 

ATU 

Cooling pump active 

0=NO 

1=YES 

  

M195 The cooling pump is active. 

  

AirTreatment.PumpCoolCap 

6D85 

ATU 

Cooling pump capacity 

M195 The capacity of the cooling pump. 

  

AirTreatment.PumpHeat 

6D8B 

ATU 

Heating pump active 

0=NO 

1=YES 

  

M195 The heating pump is active. 

  

AirTreatment.PumpHeatCap 

6D8D 

ATU 

Heating pump capacity 

M195 The capacity of the heating pump. 

  

AirTreatment.PumpHeatDefect 

6D8F 

ATU 

Heating pump failure 

0=NO 

1=YES 

  

M195.1 A error message has been detected. 

  

AirTreatment.PumpHeatInter 

6D93 

ATU 

Heating pump intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

AirTreatment.RecircValve 

6D97 

ATU 

Recirculation damper position 

M195 The valve position of the recirculation section. 

  

AirTreatment.RecircValveDef 

6D99 

ATU 

Recirculation damper error 

0=NO 

1=YES 

  

M195.1 A error message has been detected. 

  

AirTreatment.RecircValveInter 

6D9C 

ATU 

Recirculation damper intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

AirTreatment.ReturnTempCool 

6D9E 

ATU 

Cooling return water temperature 

°C 

M195 The temperature of the return water for the cooling. 

  

AirTreatment.ReturnTempHeat 

6DA0 

ATU 

Heating return water temperature 

°C 

M195 The temperature of the return water for the heating. 

  

AirTreatment.SupplyTempCool 

6E21 

ATU 

Cooling supply water temperature 

°C 

M195 The temperature of the supply water for the cooling. 

  

AirTreatment.SupplyTempHeat 

6E24 

ATU 

Heating supply water temperature 

°C 

M195 The temperature of the supply water for the heating. 

  

AirTreatment.ValveCoolDefect 

6E29 

ATU 

Cooling valve error 

0=NO 

1=YES 

  

M195.1 A error message has been detected. 

  

AirTreatment.ValveCoolInter 

6E2B 

ATU 

Cooling valve intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

AirTreatment.ValveCoolPos 

6E2F 

ATU 

Cooling valve position 

M195 The valve position of the cooling. 

  

AirTreatment.ValveHeatDefect 

6E32 

ATU 

Heating damper failure 

0=NO 

1=YES 

  

M195.1 A error message has been detected. 

  

AirTreatment.ValveHeatInter 

6E35 

ATU 

Heating damper intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

AirTreatment.ValveHeatPos 

6E39 

ATU 

Heating valve position 

M195 The valve position of the heating. 

  

CurrentStratVal.CO2 

6DB6 

Indoor CMP 

CO₂ 

ppm 

I195  

  

CurrentStratVal.HumRatDef 

6DBA 

Indoor CMP 

Humidity ratio deficit 

g/kg 

I195  

  

CurrentStratVal.HumRel 

6DBD 

Indoor CMP 

RH 

I195  

  

CurrentStratVal.Light 

6DC1 

Indoor CMP 

Light level 

I195  

  

CurrentStratVal.Light2 

6DC4 

Indoor CMP 

Light level 2 

I195  

  

CurrentStratVal.Light3 

6DC6 

Indoor CMP 

Light level 3 

I195  

  

CurrentStratVal.Light4 

6DC9 

Indoor CMP 

Light level 4 

I195  

  

CurrentStratVal.Light5 

711C 

Indoor CMP 

Light level 5 

I195  

  

CurrentStratVal.Light6 

711D 

Indoor CMP 

Light level 6 

I195  

  

CurrentStratVal.Pressure 

6DCD 

Indoor CMP 

Pressure difference 

Pa 

I195  

  

CurrentStratVal.Temp 

6DF1 

Indoor CMP 

Temperature 

°C 

I195  

  

ExtraMeas.AbsHumRat 

6DF6 

ExtrMeas 

Absolute humidity ratio 

g/kg 

M195.2  

  

ExtraMeas.AirTemp 

6DFA 

ExtrMeas 

Air temperature 

°C 

M195.2  

  

ExtraMeas.GasMeas 

6E00 

ExtrMeas 

Gas measurement 

ppm 

M195.2  

  

ExtraMeas.HumRel 

6E04 

ExtrMeas 

RH 

M195.2  

  

ExtraMeas.Intervention 

6E07 

ExtrMeas 

Intervention 

0=NO 

1=YES 

  

M195.2  

  

ExtraMeas.Percentage 

6E0B 

ExtrMeas 

Percentage 

M195.2  

  

ExtraMeas.Pressure 

6E0F 

ExtrMeas 

Pressure difference 

Pa 

M195.2  

  

ExtraMeas.State 

6E31 

ExtrMeas 

Status 

0=OFF 

1=ON 

  

M195.2  

  

ExtraMeas.Temp 

6E34 

ExtrMeas 

Temperature 

°C 

M195.2  

  

ExtraMeas.WaterTemp 

6E37 

ExtrMeas 

Water temperature 

°C 

M195.2  

  

CO2AndPurging.Intervention 

6E09 

Indoor CMP 

Intervention 

0=NO 

1=YES 

  

M195.1 Indicates whether the control has been copied to the controller by means of an override switch. 

  

CO2AndPurging.Status 

6E18 

Indoor CMP 

Status 

0=OFF 

1=ON 

  

M195  

  

CO2AndPurging.ValveError 

6E1B 

Indoor CMP 

Valve/damper error 

0=NO 

1=YES 

  

M195.1 A error message has been detected for the valve. 

  

CO2AndPurging.ValvePos 

6E1F 

Indoor CMP 

Valve position 

M195 Valve position of the CO₂ supply and air exhaust. 

  

Lighting.Defect 

6DCC 

Grow Light 

Failure 

0=NO 

1=YES 

  

M195.2  

  

Lighting.Intervention 

6DD0 

Grow Light 

Intervention 

0=NO 

1=YES 

  

M195.2  

  

Lighting.Level 

6DD4 

Grow Light 

Light level 

M195.2  

  

Lighting.State 

6DE8 

Grow Light 

Status 

0=OFF 

1=ON 

  

M195.2  

  

MeasPoint.CO2 

6DA3 

MP 

CO₂ 

ppm 

M195 The measured CO₂ concentration of the measuring box. 

  

MeasPoint.HumRatDef 

6DA5 

MP 

Humidity ratio deficit 

g/kg 

M195 The humidity ratio deficit calculated using the temperature and the relative air humidity. 

  

MeasPoint.HumRatio 

6DA6 

MP 

Absolute humidity ratio 

g/kg 

M195 The absolute moisture level calculated using the temperature and the relative air humidity. 

  

MeasPoint.HumRel 

6DA8 

MP 

RH 

M195 The measured relative air humidity of the measuring box. 

  

MeasPoint.Temperature 

6DBE 

MP 

Temperature 

°C 

M195 The measured temperature of the measuring box. 

  

UnivMeas.MeasA 

6D90 

Univ Meas 

Measurement A 

  

M195.2  

  

UnivMeas.MeasB 

6D92 

Univ Meas 

Measurement B 

  

M195.2  

  

UnivMeas.MeasC 

6D95 

Univ Meas 

Measurement C 

  

M195.2  

  

UnivMeas.MeasD 

6D98 

Univ Meas 

Measurement D 

  

M195.2  

  

ExternalAlarms.HighAlarm 

6D6F 

Indoor CMP 

High alarm 

0=NO 

1=YES 

  

I195.1 Indicates whether a high priority/low priority/Priva Office alarm is active. The High/Low alarm is an alarm in the Top Control project. The Priva Office alarm is an alarm in the Indoor growing strategy. 

  

ExternalAlarms.LockedAlarm 

6D70 

Indoor CMP 

Locked alarm active 

0=NO 

1=YES 

  

I195.1  

  

ExternalAlarms.LowAlarm 

6D72 

Indoor CMP 

Low alarm 

0=NO 

1=YES 

  

I195.1 Indicates whether a high priority/low priority/Priva Office alarm is active. The High/Low alarm is an alarm in the Top Control project. The Priva Office alarm is an alarm in the Indoor growing strategy. 

  

ExternalAlarms.POAlarm 

6D75 

Indoor CMP 

Priva Office alarm 

0=NO 

1=YES 

  

I195.1 Indicates whether a high priority/low priority/Priva Office alarm is active. The High/Low alarm is an alarm in the Top Control project. The Priva Office alarm is an alarm in the Indoor growing strategy. 

  

LightCommonData.Blocked 

6D80 

Indoor CMP 

Growing light blocked external 

0=NO 

1=YES 

  

M195.2 The Indoor control blocks the lighting, e.g. because the temperature is too high. 

  

Setpoint.InterventCO2 

6D84 

Indoor CMP 

CO₂ intervention 

0=NO 

1=YES 

  

M195.1  

  

Setpoint.InterventHumid 

6D86 

Indoor CMP 

Humidity intervention 

0=NO 

1=YES 

  

M195.1  

  

Setpoint.InterventLight 

6D89 

Indoor CMP 

Light intervention 

0=NO 

1=YES 

  

M195.1  

  

Setpoint.InterventPress 

6D8A 

Indoor CMP 

Pressure intervention 

0=NO 

1=YES 

  

M195.1  

  

Setpoint.InterventTemp 

6D8C 

Indoor CMP 

Temperature intervention 

0=NO 

1=YES 

  

M195.1  

  

BRAND_STAT.BRAND_TOEST 

3173 

BOILER 

Burner status 

0=DISCONN 

1=OFF 

2=ON 

3=HF-LS 

4=HF-HS 

5=CO₂ POS 

6=LOW SP 

7=HIGH SP 

8=NO RELEASE 

9=WAIT REL 

11=ERROR 

12=WAIT REL 

  

I310 Status of the burner. 

M250.1 The status of the burner. See M300.1 HT-warmtebeheer - HT-bronnen. 

M300.1 The status of the burner. 

M310 Modulating burners: 

  

BRAND_STAT.GER_BRAND_VERM 

3175 

BOILER 

actual capacity 

kW 

M300 The actual heat capacity by the boiler. 

M310  

M310 The actual capacity of the switching burner. 

  

BRAND_STAT.GER_GASKL_ST 

3176 

BOILER 

actual valve position 

M310  

  

CO2ktl_Prod.CdactBer 

3191 

BOILER 

CO₂ production active 

0=NO 

1=YES 

  

M250  

M310.1 Indication whether there is CO2 dosage with the boiler. 

  

KETEL.BEPERKING 

31ED 

BOILER 

Limitation boiler 

0=NONE 

1=EXTERN. BLK 

2=COOLING WATER 

3=GAS LIMITATION 

  

I310  

M310  

  

KETEL.BER_KET_TEMP 

31EE 

BOILER 

calculated boiler temperature 

°C 

I310  

M310  

  

KETEL.GEW_CO2_VERM 

31FD 

BOILER 

desired CO₂ capacity 

kW 

M300 The desired CO2 capacity of the boiler, that is dependent on the set minimum, maximum and absolute maximum CO2 capacity, the CO2 buffer influence and the calculated CO2 dosing capacity (refer to I310.2 Boiler/Forced storage). 

M310 The desired CO2 capacity of the boiler, that is dependent on the specified minimum, maximum and absolute maximum CO2 capacities, the CO2 buffer influence and the calculated CO2 dosage capacity (refer to I310.1 Boiler/Influences). 

  

KETEL.GEW_CONS_VERM 

31FE 

BOILER 

desired greenhouse capacity 

kW 

M300 The greenhouse capacity that is allocated to the boiler. 

M310 The desired heat capacity because of a capacity demand from the compartments that have been allocated to this boiler. 

  

KETEL.GEW_OPSLAG_VERM 

31FF 

BOILER 

Des forced storage capacity 

kW 

I310.2 Desired capacity of the boiler that is calculated for the filling of the heat buffer in the active period. See Gedwongen opslag in warmtebuffer. 

M300 The desired storage capacity of the boiler if the buffer strategy demands this (refer to M310 Boiler/Overview). 

M310 The required storage capacity of the boiler if the buffer strategy demands this (refer to I300 Heat management/Strategy and I310.2 Boiler/Forced storage). 

  

KETEL.GEW_RESERV_VERM 

3200 

BOILER 

Des reserve capacity 

kW 

M300 The required reserve capacity of the boiler if the heat reserve demands this. The heat reserve demands a capacity to meet the expected future heat demand. 

M310 The required reserve capacity of the boiler if the heat reserve demands this. The heat reserve demands a capacity to be able to meet an expected future heat demand. 

  

KETEL.GEW_RETOUR_VERM 

3201 

BOILER 

desired return capacity 

kW 

M310  

  

KETEL.GEW_WARMTE_VERM 

3202 

BOILER 

Des heating capacity 

kW 

M300 The desired heat capacity of the boiler, which is the sum of the demanded capacity from the greenhouse, the calculated internal capacity and the calculated return capacity (refer to M310 Boiler/Overview). 

M310 The desired heat capacity of the boiler, which is the sum of the capacity demanded by the greenhouse, the calculated internal capacity and the calculated return capacity (refer to M310 Boiler/Overview). 

  

KETEL.INT_WARMTE_VERM 

3207 

BOILER 

desired intern capacity 

kW 

M310  

  

KETEL.KET_AFN_BEP 

3208 

BOILER 

off-take limitation percentage 

M310 Percentage limitation of the heat off-take by the heating and transport systems. 

  

KETEL.KET_VERN_VRIJG 

320A 

BOILER 

Heat surplus% 

M300.1 The heat surplus percentage of the boiler. If the boiler becomes too hot due to a forced demand, the heat surplus percentage increases. 

M310 The heat surplus percentage that is present with this boiler. 

  

KETEL_.GEM_KETA_TEMP1 

3222 

BOILER 

measured boiler temperature 

°C 

I310  

M300.1 The measured boiler temperature. 

M310  

  

MOD_BRAND.BerGewBrandVerm 

3274 

BOILER 

desired burner capacity 

kW 

M310  

M310 The burner capacity that is demanded from the burner by heat management, CO2 management or for storage capacity. 

  

MOD_BRAND.BerStapBrandVerm 

3275 

BOILER 

calculated burner capacity 

kW 

M310  

  

ClimateArea.AreaTempHighVal 

3344 

CLIMATE 

temperature highest 

°C 

I12  

  

ClimateArea.AreaTempLowVal 

3346 

CLIMATE 

temperature lowest 

°C 

I12  

  

ClimateArea.BalanceTempVal 

3349 

CLIMATE 

temperature balance 

°C 

I12  

  

KRAAN.AFWIJKING 

341F 

VALVE 

Deviation 

M412 The deviation in percentages between the average measured flow and the average calculated flow of the valve. For the calculated flow the Correction more valves in (I430.1 Water system/Settings) has been taken into account. A positive deviation means that the measured flow was greater than the calculated flow. 

  

KRAAN.FLOW 

3428 

VALVE 

Flow 

m³/hr 

M412 The average measured flow of this valve. 

  

KRAAN.GEMID_EC 

342C 

VALVE 

A_EC 

mS/cm 

M412 The average EC value. 

  

KRAAN.GEMID_PH 

342D 

VALVE 

A_pH 

pH 

M412 The average pH value. 

  

KRAAN.KR_EENH_VERBR 

3438 

VALVE 

amount of water per unit 

ml 

M412 The water consumption per set unit. 

  

KRAAN.KRAAN_AANWEZIG 

343A 

VALVE 

  

0=NO 

1=YES 

  

  

KRAAN.KRAAN_TOESTAND 

343E 

VALVE 

Status 

0=REST 

1=RECIPE 

2=START 

3=IRRIG 

4=STAND TIME 

5=RECIPE SIPH 

6=STARTSIPH 

7=SIPHON 

8=ERROR 

9=WAIT 

10=RETURN 

11=RECIPER 

12=START R 

13=RINSE 

14=RUN TIME 

  

I412  

I412.1 Indication of the status of the valve. See I412 Kraan start, stop en reset. 

I414 See Status in I412 Kraan start, stop en reset. 

M411 The status of the valve, see I412 Kraan start, stop en reset. 

  

KRAAN.REG_GEG 

3447 

VALVE 

  

  

  

KRAAN.TODOH_KRAANVAK 

3459 

VALVE 

amount of water per valve 

M411  

  

KRAAN.VERBRUIK 

345F 

VALVE 

Quantity 

M412 The total water consumption of this valve. 

  

KRAAN.VERBRUIKM2 

3461 

VALVE 

Liters per m² 

l/m² 

M412 The total water consumption of this valve in l/m2. 

  

LBS_Metingen.RVKasGemGed 

36F1 

ATU STRAT 

Measured RH 

I15  

I15.1  

I15.1  

M15.1  

  

LBS_Metingen.TKasGemGed 

36F2 

ATU STRAT 

measured cooling temperature 

°C 

I15  

I15.1  

I15.1  

M15.1  

  

LBS_Periode.RvBevoGew 

3704 

ATU STRAT 

Humidify level 

I15 calculated humidity level at which the ATU is allowed to start humidifying the greenhouse air 

M15.1 humidity level at which the ATU is allowed to start humidifying the greenhouse air 

M15.2 humidity level at which the ATU is allowed to start humidifying the greenhouse air 

  

LBS_Periode.RvOntvoGew 

3705 

ATU STRAT 

Dehumidification level 

I15 calculated humidity level at which the ATU is allowed to start dehumidifying the greenhouse air 

M15.1 humidity level at which the ATU is allowed to start dehumidifying the greenhouse air 

M15.2 humidity level at which the ATU is allowed to start dehumidifying the greenhouse air 

  

LBS_Periode.TKoelGew 

3706 

ATU STRAT 

cooling temperature 

°C 

I15  

M15.1 temperature at which the ATU is allowed to start cooling the greenhouse air 

  

LBS_Periode.TVerwGew 

3707 

ATU STRAT 

heating temperature 

°C 

I15  

M15.1 temperature at which the ATU is allowed to start heating the greenhouse air 

  

GEN_STU_UI_01.CD_BEPERKING 

37F2 

ATU 

Limitation 

0=NONE 

1=ERROR 

2=I/O DEFECT 

3=I/O ASSIGN. 

4=MANUAL 

5=MIN LIMIT 

6=MAX LIMIT 

7=ACT TIME-OUT 

8=ANTI STUCK PROTECT 

9=RELEASE 

  

I157  

I158  

M157  

M158  

M158  

  

GEN_STU_UI_01.PERC_STU_GEM 

37FD 

ATU 

Measured position 

I157 measured position of the inlet or the air outlet 

I158 measured position of the inlet or air outlet 

M157 measured position of the mixing chamber inlet or the air outlet 

M158 measured position of the inlet 

M158 measured position of the air outlet 

  

GEN_STU_UI_01.PERC_STU_GEW 

37FE 

ATU 

Desired position 

I157 The desired position of the inlet or the air outlet. This position is calculated based on the maximum and minimum mixing ratio and the damped mixing ratio (see Maximum mixing ratio , Minimum mixing ratio and Calculated smoothed mixing ratio ). 

I158 The desired position of the inlet or air outlet. This position is calculated based on the maximum and minimum mixing ratio and the smoothed mixing ratio (see Maximum mixing ratio , Minimum mixing ratio and Calculated smoothed mixing ratio in I157). 

M157 The desired position of the mixing chamber inlet or the air outlet. This position is calculated based on the maximum and minimum mixing ratio and the smoothed mixing ratio (see Maximum mixing ratio , Minimum mixing ratio and Calculated smoothed mixing ratio in Strategie). 

M158 Desired position of the inlet 

M158 The desired position of the air outlet. This position is calculated based on the maximum and minimum mixing ratio and the smoothed mixing ratio (see Maximum mixing ratio , Minimum mixing ratio and Calculated smoothed mixing ratio in I157). 

  

MENGKLEP_IN.T_MK_GEW 

38A8 

ATU 

Calc supply temperature 

°C 

M155 calculated temperature of the water flowing into the block 

M155 calculated temperature of the water flowing into the block 

  

LB_FAN_MREF.AVKasGem 

3CC4 

ATU 

absolute humidity blow-out 

g/m³ 

M153 measured AH of the airflow 

  

LB_FAN_MREF.RVKasGem 

3CCB 

ATU 

relative humidity blow-out 

M153  

  

LB_FAN_MREF.TKasGem 

3CCC 

ATU 

blow-out temperature 

°C 

M153 measured temperature of the airflow 

  

LB_OUT_FAN_GROEP.BerMaxPercBasis 

3D2E 

ATU 

total maximum fan capacity 

I153 Control area of the fan capacity if Release increase fan capacity has been released. If there is no deviation between the desired and the measured value, the minimum fan capacity applies. If the deviation between the desired and the measured value is greater than or equal to the set P band, the maximum fan capacity applies. 

  

LB_OUT_FAN_GROEP.BerMinTotaal 

3D30 

ATU 

total minimum fan capacity 

I153 Control area of the fan capacity if Release increase fan capacity has been released. If there is no deviation between the desired and the measured value, the minimum fan capacity applies. If the deviation between the desired and the measured value is greater than or equal to the set P band, the maximum fan capacity applies. 

  

LB_OUT_FAN_GROEP.FFanBer 

3D4E 

ATU 

Calculated flow fan 

m³/hr 

M150.1 The calculated quantity of air that is displaced by the fan or fans of the same ATU. This quantity is calculated on the basis of the Calculated flow inlet grh air (M153) and Calculated flow inlet outside air (M153) that flow into the mixing chamber. 

M153 The calculated quantity of air that is displaced by the fan or fans of the same ATU. This quantity is calculated based on the calculated amount of greenhouse air and of outside air flowing into the mixing chamber. 

  

LB_OUT_FAN_GROEP.FFanGer 

3D54 

ATU 

actual flow fan 

m³/hr 

M150.1 actual quantity of air that has been displaced by the fan or fans of the same ATU 

M153 actual quantity of air that is displaced by the fan or fans of the same ATU 

  

LB_OUT_FAN_GROEP.PercFanBer 

3D64 

ATU 

calculated fan capacity 

I153  

I153.2  

M150.1 This capacity is calculated on the basis of the desired capacity of the fan (I153) plus any increase ( Calc increase cap by temp difference in I153). 

M153  

  

LB_OUT_FAN_GROEP.PercFanGer 

3D65 

ATU 

actual fan capacity 

I153  

I153.1  

I153.2  

M150.1 The current position of the blow-out fan. 

M153  

  

LB_OUT_FAN_GROEP.PercFanGew 

3D66 

ATU 

desired fan capacity 

I153  

I153  

I153.1  

I153.2  

M153  

  

MaxUitblaasT.IngMaxUitblaasT 

3E12 

ATU 

Maximum blow-out temperature 

°C 

I151 Maximum blow-out temperature is set above 

  

MaxUitblaasT.T_BasisSLangGew 

3E13 

ATU 

unlimited maximum blow-out temperature 

°C 

I151  

  

MaxUitblaasT.TMaxUitblBer 

3E15 

ATU 

limited maximum blow-out temperature 

°C 

I151  

  

MinUitblaasT.CdjnActief 

3E56 

ATU 

Blow-out strategy active 

0=NO 

1=MINIMUM 

2=MIN COOL 

3=MAXIMUM 

  

I150  

  

MinUitblaasT.GewMinUitbltemp 

3E63 

ATU 

limited minimum blow-out temperature 

°C 

I150  

  

MinUitblaasT.T_BasisSLangGew 

3E69 

ATU 

unlimited minimum blow-out temperature 

°C 

I150  

  

LogDevUI.CalcPosition 

73DA 

AIR CIRCUL. 

Calculated position 

I190.3 The position to be achieved. 

M190 The position to be achieved. 

M192 The position to be achieved. 

  

LogDevUI.MeasPosition 

73DB 

AIR CIRCUL. 

Measured position 

I190.3 The measured position. 

M190 The measured position. 

M192 The measured position. 

  

PosCntr.DriveState 

73DC 

AIR CIRCUL. 

Status 

0=IDLE 

1=DEACTIVATED 

2=PENDING 

3=ACTIVE 

4=AT MAXIMUM 

5=RUNNING UP 

6=AT POSITION 

7=RUNNING DOWN 

8=AT MINIMUM 

9=STOPPING 

  

I190.3 The current state of the fan/air mixer. See Status 

M190 The current state of the fan/air mixer. See State 

M192 The current state of the fan/air mixer. See Status 

  

Luchtcirculatie.ToestandVentUI 

40C4 

AIR CIRCUL. 

Status air circulation control 

0=OFF 

1=ON 

2=MIN T ON 

3=MIN T OFF 

  

I190  

M190 See 19 Status air circulation control . 

M192 See 19 Status air circulation control . 

  

MeMstPARSomRef.PARRefSomBer 

417B 

PAR SENSOR 

PAR sum today 

mol/m² 

M4 The sum of the smoothed PAR from today, counting from the Time sunrise until now. 

  

PARMe.PARGem 

418C 

PAR SENSOR 

PAR 

umol/s/m² 

M4  

M105.1 The measured PAR. 

  

WthrRadCopy.CtrlRadiation 

41F6 

RAD SENS 

radiation 

W/m² 

M4  

M100 The measured radiation. 

  

WthrRadCopy.MeasRadiation 

41F1 

RAD SENS 

radiation measured 

W/m² 

M4  

  

WthrRadCopy.RadSumToday 

41F8 

RAD SENS 

radiation sum today 

J/cm² 

M4 The measured sum of the smoothed radiation for today, counted from Time sunrise to now. 

M100 The measured radiation sum counted from the moment of sunrise (M4 Overzicht/Metingen). 

  

WthrStation.MeasRainQuantity 

6FDB 

STATION 

Rain quantity 

mm/min 

M4.2 The measured rain quantity per weather station. 

  

WthrStation.MeasRainState 

6FDC 

STATION 

Rain 

0=NO 

1=YES 

  

M4.2 Indication of whether the result of the rain measurement is active per weather station. 

  

EL_VOCHT.BER_ABSVO 

4270 

WEATHER 

  

g/m³ 

  

EL_VOCHT.MeasEnthalpy 

6378 

WEATHER 

  

kJ/kg 

  

WthrObserv.CalcEnthalpyOuts 

6FBF 

WEATHER 

Enthalpy of outside air 

kJ/kg 

M4 The calculated enthalpy of the outside air based on the measured air humidity and temperature. 

  

WthrObserv.CalcOutsAbsHum 

7009 

WEATHER 

absolute humidity 

g/m³ 

M4 The measured absolute humidity of the outside air. 

M100 The measured absolute air humidity outside. 

  

WthrObserv.CalcOutsHumDef 

427F 

WEATHER 

humidity deficit 

g/m³ 

M4 The measured humidity deficit of the outside air. 

M100 The measured humidity deficit outside. 

  

WthrObserv.CalcSkyTemp 

42FC 

WEATHER 

Sky temperature 

°C 

M4 The measured sky temperature. 

  

WthrObserv.CalcWindChillT 

42A0 

WEATHER 

Calculated windchill 

°C 

M4 The wind chill is a measure of the quantity of heat that a body loses at the measured outside temperature and wind speed. The wind chill is calculated at an outside temperature below 10°C and with a wind speed higher than 1 m/s. At an outside temperature above 10°C and with a wind speed below 1 m/s, the calculated wind chill is equal to the measured outside temperature. The radiation and the air humidity have no influence in the calculation on the calculated wind chill. 

  

WthrObserv.CtrlCO2Conc 

4293 

WEATHER 

Outside CO₂ concentration control 

ppm 

M4  

M4 The measured CO₂ level of the outside air. 

  

WthrObserv.CtrlIrradiation 

42FD 

WEATHER 

irradiation 

W/m² 

M4  

M100 The measured irradiation. 

  

WthrObserv.CtrlOutsideTemp 

42A9 

WEATHER 

outside temperature 

°C 

M4  

M100 The measured outside temperature. 

  

WthrObserv.CtrlRainPercent 

427C 

WEATHER 

rain percentage control 

M4  

  

WthrObserv.CtrlWindAngle 

42AB 

WEATHER 

wind direction control 

° 

M4  

  

WthrObserv.CtrlWindSpeed 

42AD 

WEATHER 

wind speed 

m/s 

M4  

M100 The measured wind speed. 

  

WthrObserv.FrostActive 

42F0 

WEATHER 

frost 

0=NO 

1=1--- 

2=-2-- 

3=12-- 

4=--3- 

5=1-3- 

6=-23- 

7=123- 

8=---4 

9=1--4 

10=-2-4 

11=12-4 

12=--34 

13=1-34 

14=-234 

15=1234 

  

M4  

M100 Indication whether it is freezing and if so, which frost limit is active. These can be several frost limits. 

  

WthrObserv.MeasOutsideTemp 

429D 

WEATHER 

Outside temperature 

°C 

M4  

  

WthrObserv.MeasOutsRelHum 

427E 

WEATHER 

outside humidity RH measurement 

M4  

  

WthrObserv.MeasRainQuantity 

42C0 

WEATHER 

Rain quantity 

mm/min 

M4 The measured rain quantity in mm/min. 

  

WthrObserv.RainActive 

42EE 

WEATHER 

rain 

0=NO 

1=YES 

  

M4  

M100 Indication whether (forced) rain is active. 

  

WthrObserv.StormActive 

42EF 

WEATHER 

storm 

0=NO 

1=1--- 

2=-2-- 

3=12-- 

4=--3- 

5=1-3- 

6=-23- 

7=123- 

8=---4 

9=1--4 

10=-2-4 

11=12-4 

12=--34 

13=1-34 

14=-234 

15=1234 

  

M4  

M100 Indication whether there is a storm and if so, which storm limit is active. These can be several limits. 

  

WthrObserv.SunHeightNow 

425A 

WEATHER 

Sun height now 

° 

M4 Current calculated angle at which the solar radiation strikes the earth’s surface. The heating control, ventilation control and light control may take the height of the sun into account 

  

WthrObserv.WindSection 

429B 

WEATHER 

wind direction 

0=N 

1=NE 

2=E 

3=SE 

4=S 

5=SW 

6=W 

7=NW 

  

M4 The measured wind direction. 

M100 The measured wind direction. 

  

LogDevUI.MeasPosition 

76CE 

Channel 

Measured position 

I208  

I208.3 The measured position. 

  

ModLightMeasure.ActRecipeNumber 

7BC6 

MOD. LIGHT 

Recipe number 

  

M208 The active recipe number. 

  

ModLightMeasure.DesLightPerc 

7AB7 

MOD. LIGHT 

Des. light% 

M208 The desired light percentage of the modulating growing light system. 

  

ModLightMeasure.DesNrOfSteps 

7AB8 

MOD. LIGHT 

Des. steps 

  

M208 The requested number of growing light steps for electricity off-take. 

  

ModLightMeasure.SystemLimitation 

76E2 

MOD. LIGHT 

Limitation 

0=NONE 

1=INSTALLATION 

2=NOT OPERABLE 

3=LOCAL BLOCK 

4=EMERGENCY HOLD 

5=WAIT HEATING 

6=WAIT CURTAIN 

7=WAIT REL 

8=FIXED POSITION 

9=CROP TREATM. 

10=FORCED ON 

11=FORCED OFF 

12=RECIPE 

13=AT MAXIMUM 

14=AT MINIMUM 

15=MINIMUM OFF-TAKE 

16=NO STRATEGY 

17=OFF DELAY 

  

I208 The limitation for the modulating growing light system. 

M208 See 13 Limitation . 

  

PARRegGrLiStap.GrLiStapToestCd 

469E 

LIGHT STEP 

Status growing light step 

0=OFF 

1=ON 

2=WAIT ON 

3=WAIT OFF 

  

M20  

  

PARRegSchKop.SchermStandGer 

46B1 

CURTAIN 

Calculated shading position 

M20 Calculated position of the shading curtain. 

  

PARRegSchKop.SchermToestCd 

46B4 

CURTAIN 

Status shading 

0=OPEN 

1=MINIMUM 

2=CONTROL 

3=CLOSE 

4=WAIT OPEN 

  

M20  

  

PARCalcSetpoint.ParRegSet 

6928 

LIGHT CNTRL 

Set PAR 

umol/s/m² 

M20 Set PAR value from the current period or correction setting. 

  

PARRegelingAlg.CalcLightPerc 

79F3 

LIGHT CNTRL 

Calculated light percentage 

M20 The calculated light percentage from the calculated PAR value, if necessary adjusted by the decrease based on the measured light and PAR correction and limited to the calculated maximum light percentage. 

  

PARRegelingAlg.CalcParLighting 

46E9 

LIGHT CNTRL 

Calculated PAR lighting 

umol/s/m² 

I20  

  

PARRegelingAlg.CalcParShading 

46F3 

LIGHT CNTRL 

Calculated PAR shading 

umol/s/m² 

I20  

  

PARRegelingAlg.CalcParSum 

46FA 

LIGHT CNTRL 

Calculated PAR sum 

mol/m² 

I20  

M20 The Calculated PAR sum is based on the set Desired PAR sum (I20) and adjusted by all the calculated influences. This value determines whether the growing light switches off or remains off and controls the position of the shading curtains. 

  

PARRegelingAlg.InflLiRefOnLiP 

79F5 

LIGHT CNTRL 

Influence light reference 

M20 The influence on the light percentage, based on the specified reference measurement (I20.4) and PAR reference : decrease light% or Rad. reference : decrease light% (I20.2). 

  

PARRegelingAlg.InflParCorrOnLiP 

7B4C 

LIGHT CNTRL 

Influence PAR correction 

M20 The PAR correction ensures that the calculated light percentage goes to the desired PAR value. The PAR correction depends on the specified reference measurement (I20.4), the calculated added PAR output by the growing light system, the specified PAR correction factor (dealer setting) and the option Use PAR correction for light% (I20.4). 

  

PARRegelingAlg.ParRegLimitCd 

46F0 

LIGHT CNTRL 

limitation 

0=NOT PRESENT 

1=MEASUREMENT 

2=PAR SUM 

3=EXT LIGHT 

4=EXT SHADING 

5=REFERENCE 

6=GR. LIGHT 

7=SHADING 

8=INSTALLATION 

9=NONE 

  

M20  

  

PARRegelingAlg.ParRegStateCd 

46F2 

LIGHT CNTRL 

status 

1=OFF 

2=NIGHT 

3=SHADING 

4=LIGHT 

5=ACTIVATED 

  

M20  

  

PARRegReferentie.ParGebruikt 

4709 

LIGHT CNTRL 

applied PAR 

umol/s/m² 

I20.4 Measured PAR used by the light control to calculate the number of growing light steps and the light percentage. 

M20 Measured PAR used by the light control to control the position of the shading curtains and to switch the growing light on and off. 

  

PARRegReferentie.ParSomVandaag 

470E 

LIGHT CNTRL 

PAR sum today 

mol/m² 

M20  

  

PARRegReferentie.RadGebruikt 

7A0C 

LIGHT CNTRL 

Used radiation 

W/m² 

I20.4 Measured radiation used by the light control to calculate the number of growing light steps and the light percentage. 

M20 Measured radiation used by the light control to control the position of the shading curtains and to switch the growing light on and off. 

  

PARRegSchFunc.SchStralBeperBer 

471C 

LIGHT CNTRL 

Actual radiation limitation 

M20 Calculated limitation of the radiation by all closed shading curtains. 

  

METERSTAND.METERSTAND 

4750 

ENER.PULSE M 

Meter reading 

  

  

METERSTAND.VerbruikVd 

4756 

ENER.PULSE M 

Total 

  

  

PULSMETER.FLOW 

4764 

ENER.PULSE M 

Current consumption 

unit/hour 

  

COM_DOS_RCPT.REGEL_EC 

47AB 

RECIPE 

Calculated EC 

mS/cm 

I403 Calculated EC value; the desired EC with the radiation decrease of the EC and the measured EC of the supply water if Toevoegen EC in I403.1 Recept/Waterbehandeling is set to YES. 

  

RETOUR.BESTEM_SILO 

481D 

RETURN 

Tank 

  

M440  

  

RETOUR.BESTEM_TYPE 

481E 

RETURN 

Destination 

0=OUTLET 

1=TANK 

2=ALT OUTLET 

3=ALT TANK 

  

M440 The destination of the return water. 

  

RETOUR.TOESTAND 

4837 

RETURN 

Status return 

0=REST 

1=ON-GOING 

2=BUSY 

3=RETURN 

4=DELAY CLEANING 

5=CLEANING 

  

I443 Status indication of the return main. 

M440 The status of the return main. 

  

SILOVK.ACTIE 

4850 

FILL VALVE 

Action 

0=NONE 

1=FILL UP 

2=FILL UP% 

3=FILL TO MAX 

4=FILL TO MAX% 

5=ALWAYS 

6=STORE 

  

I440 Indication of the action of the fill valve. 

  

SILOVK.BEPERKING 

4852 

FILL VALVE 

Limitation 

0=NONE 

1=CALIBRATE LEVEL 

2=MAX CONTENT 

3=LEVEL SENSOR 

4=RECYCLE TANK 

5=FRESH WATER TANK 

6=CONSUMPTION MAX 

7=CONSUMPTION MIN 

8=CONSUMPTION ZERO 

  

I440 The limitation of the fill valve. 

  

SILOVK.TOESTAND 

485D 

FILL VALVE 

Status 

0=REST 

1=RECIPE 

2=START 

3=FILL 

4=ERROR 

  

I440 The status of the fill valve. 

M430 The status of the tank fill valve. 

M440 Status of this fill valve. 

  

TankStatusCopy.WATER_NIV 

68A0 

TANK 

Water level 

I440 Percentage of water level of the tank. A trend is also displayed. 

M430 See Water level in I440 Silo/Instellingen. 

M440 The water level in the tank as a percentage. A trend is also displayed. 

M440.1 The measured water level in percentages and the trend of this in the tank. 

  

TankStatusCopy.WATER_STAND 

68A1 

TANK 

Water state 

0=--- 

1=FULL 

2=ENOUGH 

3=FILL TO MAX 

4=DOSING 

5=FILL UP 

6=BLOCK 

7=BLOCK/FILL UP 

8=EMPTY 

  

I440 Water state in the tank. See M440 Overzicht silo. 

M430 The water state in the tank. 

M440 Water state in the tank. 

  

START_VOORW.START_VOORW 

4AF2 

start cause 

0=NONE 

1=TEMP 

2=HUMIDITY 

3=RADIATION 

4=RADSUM+DR 

5=CLOCK 

6=EXTERNAL 

7=MAX REST 

8=MANUAL 

9=TRANSPIRATION 

10=MOIST%-SLAB 

11=TENSIO 

12=START SEQUENCE 

13=VPD SUM 

14=DRY-OUT 

15=TRANSPIRATION SUM 

16=PAR 

17=PAR-SUM+DR 

  

M400 The cause for starting the irrigation. 

M400.2 The cause for starting the irrigation. See M400 Autostart/Actueel 

  

STARTMGRB.START_NUM 

4B01 

Cycle 

  

M400 This indicates the cycle number of the irrigation cycle. The number sequence is per day from 1 up to the number of cycles run on that day. 

  

STRAL_ST.GEC_STRALSOM 

4BD5 

START PRG 

radiation sum limit 

J/cm² 

M400  

  

STRAL_ST.STRALSOM 

4BD8 

START PRG 

radiation sum 

J/cm² 

M400  

  

VERDAMP_ST.BER_DRAIN_PRC 

4BF8 

START PRG 

desired drain% 

M400 The quantity increase ensures that the desired drain percentage is increased. This allows a possible shortage to be made up for. 

  

STRT_IRRIG.MEASDRYOUT_UNIT 

6648 

SUBSTR START 

Dry-out 

ml/unit 

M500 The dry-out of the pot or the substrate at the start of the irrigation cycle. 

  

STRT_IRRIG.START_CAUSE 

665D 

SUBSTR START 

start cause 

0=UNKNOWN 

1=MANUAL 

2=MOIST%-SLAB 

3=DRY-OUT 

4=RESTTIME 

5=RADIATION SUM 

6=EXTERNAL 

7=DRAINAGE 

8=SAFETY LEVEL 

  

M500 The cause of every start. 

  

STRT_IRRIG.START_NUM 

6661 

SUBSTR START 

Cycle 

  

M500 The sequence number of the irrigation cycle for this day. 

  

IrrigatMeasCalc.CalcDryingInKg 

6644 

SUBSTR START 

dry-out limit 

kg 

I500  

I500  

I500.2  

M500  

  

IrrigatMeasCalc.CalcTranspPerM2 

67CE 

SUBSTR START 

transpiration rate 

l/m²/hr 

M500 The decrease in the measured humidity expressed in litres per m² per hour. 

  

IrrigatMeasCalc.CurrentDesirWCon 

6653 

SUBSTR START 

moisture level limit 

I500  

I500  

I500.2  

M500  

  

IrrigatMeasCalc.CycleRadSum 

665A 

SUBSTR START 

radiation sum after last irrigation cycle 

J/cm² 

M500 The current measured radiation sum after the start of the last irrigation cycle 

  

IrrigatMeasCalc.DampedTranspirat 

665E 

SUBSTR START 

Measured transpiration rate 

ml/unit/h 

I500  

  

IrrigatMeasCalc.DesirDryoutUnit 

666C 

SUBSTR START 

dry-out limit 

ml/unit 

I500  

I500  

I500.2  

M500  

  

IrrigatMeasCalc.DesWghtUniInKg 

6678 

SUBSTR START 

desired weight per unit 

kg 

M500  

  

IrrigatMeasCalc.IrrigatPerState 

6689 

SUBSTR START 

status 

0=OFF 

1=MANUAL 

2=WAIT 

3=NOT AVAILABLE 

4=WAIT FOR TRANSPIR. 

5=RAMPING 

6=PERIOD RELEASE 

7=FLUSHING RELEASED 

8=IRRIGATION STOPPED 

9=MIN START 

10=END OF DAY 

11=SAFETY START 

  

I500 See 32 Period/status . 

M500 See 32 Period/status 

  

IrrigatMeasCalc.MeasDryoutUnit 

669E 

SUBSTR START 

measured dry-out 

ml/unit 

I500  

I500  

I500.2  

M500  

  

IrrigatMeasCalc.MeasWContent 

66A2 

SUBSTR START 

measured moisture level 

I500  

I500  

I500.2  

M500  

  

IrrigatMeasCalc.MeasWghtTot 

66A8 

SUBSTR START 

measured total weight 

kg 

I500  

I500  

I500.2  

M500  

  

IrrigatMeasCalc.MeasWghtUni 

66AA 

SUBSTR START 

measured weight per unit 

kg/unit 

M500  

  

IrrigatMeasCalc.MinTranspStart 

66AD 

SUBSTR START 

transpiration rate limit 

ml/unit/h 

I500  

  

IrrigatMeasCalc.SelMaxCycleRadSu 

66BB 

SUBSTR START 

radiation sum limit 

J/cm² 

M500  

M500 The maximum radiation sum between the start of the last irrigation cycle and the start of the new irrigation cycle that is applicable for the current period. 

  

IrrigatMeasCalc.UsedDrWghtTo_01 

66D8 

SUBSTR START 

Used saturation weight total 

kg 

I500 The total measured weight from the weighing scale at the last drain measurement (this value corresponds to the weight in M500.1). 

  

ALG_POMP_.GER_POMPST 

4C4F 

PUMP 

Actual pump position 

0=OFF 

1=ON 

2=LOW SP 

3=HIGH SP 

  

I350 Actual position of the transport pump, see 6 Actual pump position . 

M350 Actual position of the transport pump (only for switching pump). 

  

ALG_POMP_.POMP_BEPERK 

4C51 

PUMP 

Limitation pump drive 

0=NONE 

1=RELEASE 

2=FIXED POS 

3=MAX CAP 

4=DEFECTIVE 

5=EXT ERROR 

6=CALIB ERROR 

7=ALLOC INPUT 

8=ALLOC OUTPUT 

9=DRIVE 

10=MEASUREMENT 

11=HEAT SURP 

12=TEMP 

13=EXT DRIVE 

14=NOT CONTROLLED 

15=LOW TEMP HEAT SURP 

  

I350 Indication of the limitation of the transport pump, see 10 Limitation pump drive . 

M350 Indication of the limitation of the transport pump. 

  

TRANSCTL.GV_VERM_TOT 

4CE3 

TRANSP.MAIN 

Des transport capacity 

kW 

M350 The required transport capacity that is passed on to the heat producers. 

  

TRANSCTL.MK_TEMP_TOT 

4CE7 

TRANSP.MAIN 

Desired transport temp 

°C 

M350 The desired temperature of the transport main from the heat management. The desired transport temperature is equal to the highest demanded water temperature from the connected compartments, heat block or combi block from the connected air treatment units plus the set Offset transport temperature . 

  

TRANSSYS.GEM_TRAN_TEMP 

4CF0 

TRANSP.MAIN 

measured supply temperature 

°C 

I350  

M350  

  

MomReserv.WProdBegr 

4F2E 

MANIFOLD 

total heat production limited 

kW 

M300.3  

  

MomReserv.WProdOnbegr 

4F32 

MANIFOLD 

total heat production unlimited 

kW 

M300.3  

  

WARMTECTL.GEW_LOS_VERM 

4FC8 

MANIFOLD 

Act capacity emptying 

kW 

M300 The capacity that the buffer supplies. This is calculated on the basis of the position of the off-take mixing valve. If the off-take mixing valve is open for 50%, then half of the demanded capacity from the greenhouse is supplied by the buffer. 

  

WARMTECTL.GEW_TEMP 

4FC9 

MANIFOLD 

total desired greenhouse temperature 

°C 

M300  

  

WARMTECTL.GEW_VERM 

4FCA 

MANIFOLD 

total desired greenhouse capacity 

kW 

M300  

  

MISTKLEP.GEW_CAP 

5009 

MIST VALVE 

Calculated capacity 

M180 Calculated capacity mist valve. 

  

MISTKLEP.TOESTAND 

5010 

MIST VALVE 

Status 

0=NO RELEASE 

1=WAIT PUMP 

2=OFF 

3=SPRAY PAUSE 

4=SPRAY 

5=PRESSURE RELIEF 

  

I185 The status of the mist valve. 

M180 The status of the mist valve. 

  

KASL_REF.REG_GEWAS_RV 

50B6 

HUMIDIF 

Used relative humidity 

I180.4 The humidity that is used for the humidification control. 

  

KASL_REF.REG_GEWAS_TEMP 

50B7 

HUMIDIF 

Measured temperature 

°C 

I180.4 The temperature that is used for the humidification control. 

M180 The measured temperature that is used for the misting control. 

  

KASL_REF.REG_GEWAS_VD 

50B8 

HUMIDIF 

Used humidity deficit 

g/m³ 

I180.4  

  

VOCHT_CTL.BER_RV 

50EB 

HUMIDIF 

Calculated humidity limit 

I180 The calculated humidity limit for switching the misting installation. 

I181  

M180 The calculated humidity limit for switching the misting installation. 

  

VOCHT_CTL.BER_VD 

50EC 

HUMIDIF 

Calculated humidity limit 

g/m³ 

I180 The calculated humidity limit for switching the misting installation. 

I181  

M180 The calculated humidity limit for switching the misting installation. 

  

VOCHT_CTL.GEM_RV 

50F2 

HUMIDIF 

Measured humidity 

M180 The measured air humidity that is used for the misting control. 

  

VOCHT_CTL.GEWENSTE_TEMP 

50F5 

HUMIDIF 

Calculated cooling temperature 

°C 

I180  

I181  

M180 The calculated cooling temperature for switching the misting installation. 

  

VOCHT_CTL.INSTEL_TEMP 

50F9 

HUMIDIF 

Set cooling temperature 

°C 

I180  

M180 The set cooling temperature from I180 Misting/Strategy. 

  

VOCHT_CTL.SETP_RV 

510D 

HUMIDIF 

Set humidity limit 

M180 The set humidity limit from I180 Misting/Strategy. 

  

VOCHT_CTL.SETP_VD 

5111 

HUMIDIF 

Set humidity limit 

g/m³ 

M180 The set humidity limit from I180 Misting/Strategy. 

  

BUFOPN.GEM_TEMP 

51D5 

SENSOR 

Meas temperature buffer sensors 

°C 

M320  

  

BUF_TOEST.LEGEN 

5206 

BUFFER 

Emptying active 

0=NO 

1=YES 

  

I320 Indication whether the emptying of the buffer is active. 

M300.1 Indication whether the emptying of the buffer is active. 

M320 Indication whether the emptying of the buffer is active. 

  

BUF_TOEST.VULLEN 

5212 

BUFFER 

Filling active 

0=NO 

1=YES 

  

I320 Indication whether the filling of the buffer is active. 

M300.1 Indication whether the filling of the buffer is active. 

M320 Indication whether the filling of the buffer is active. 

  

BUFFER.GEM_LTEMP_RET 

5223 

BUFFER 

Measured return temperature emptying 

°C 

M320 The measured temperature of the return water from the compartments to the heat buffer during emptying. 

M325.1 The measured temperature of the return water from the compartment(s) to the heat buffer during emptying. 

  

BUFFER.GEM_TEMP_AANV 

5225 

BUFFER 

Measured supply temperature 

°C 

M320 The measured temperature of the supply water from the heat source(s) to the heat buffer(s) (during filling), or from the heat buffer to the compartments (when emptying). 

M325.1 The measured temperature of the supply water from the heat source(s) to the heat buffer(s) (during filling), or from the buffer to the compartments (when emptying). 

  

BUFFER.GEM_VTEMP_RET 

5228 

BUFFER 

Measured return temperature filling 

°C 

M320 The measured temperature of the return water from the heat buffer to the heat source(s) during filling. 

M325.1 The measured temperature of the return water from the heat buffer to the heat source(s) during filling. 

  

BUFFER.GER_VUL_PERC 

5229 

BUFFER 

Actual fill% 

I320 Actual fill percentage. 

I320.1 The actual buffer filling percentage is calculated on the basis of the difference between the heat capacity that is loaded into the buffer and the heat capacity that is leaving the buffer at that instant. This percentage is limited between the minimum and maximum achievable filling percentage, determined on the basis of the measurements from the temperature sensors. 

M320 The actual fill percentage of the heat buffer. 

  

BUFFER.GEW_VUL_PERC 

522C 

BUFFER 

Desired fill% 

M320 The desired fill capacity of the heat buffer. 

  

BUFFER.LEEG_BEPERK 

5230 

BUFFER 

Limitation emptying 

0=NONE 

1=RELEASE 

2=TOO COLD 

3=EXT BLOCK 

4=EMPTY 

5=MIN FILL% 

6=FILL 

  

I320 Possible cause why the buffer is not being emptied. 

M300.1 The limitation why the buffer is not being emptied. 

M320 The limitation why the buffer is not being emptied. 

  

BUFFER.VUL_BEPERK 

524A 

BUFFER 

Limitation filling 

0=NONE 

1=RELEASE 

2=TEMP 

3=FULL 

4=MAX FILL% 

5=EMPTYING 

  

I320 Possible cause why the buffer is not being filled. 

M300.1 The limitation why the buffer is not being filled. 

M320 The limitation why the buffer is not being filled. 

  

WARMW_TE_VM.GEW_KET_VERM 

52C5 

HEAT EXCH 

desired greenhouse capacity 

kW 

M300  

M340 The desired heat capacity that has been allocated to this heat exchanger because of a capacity demand from the compartments. 

  

WARMWIS_ALG.BEPERKING_WW 

52CC 

HEAT EXCH 

limitation heat exchanger 

0=NONE 

1=MANUAL 

2=MAX CAP 

3=NO RELEASE 

4=EXTERNAL 

5=HX DISCONNECTED 

6=ALLOC INPUT 

7=ALLOC OUTPUT 

8=CALIB SERVO 

9=ALLOC SERVO 

10=LIMIT SERVO 

11=CONTROL SERVO 

12=INPUT HX DEFECT 

13=NO TEMP 

14=TOO WARM 

15=COOLING WATER 

  

M300.1 See 14 Limitation HX 

M340  

  

WARMWIS_ALG.BER_WW_TEMP 

52CE 

HEAT EXCH 

calculated heat exchangers temperature 

°C 

I340  

M300.1 The calculated supply temperature of the heat exchanger. 

M340 The temperatures of the heat exchanger. 

  

WARMWIS_ALG.GER_KET_TEMP 

52D6 

HEAT EXCH 

heat exchangers temperature 

°C 

I340  

M300.1 The measured supply temperature of the heat exchanger. 

M340 The temperatures of the heat exchanger. 

  

WARMWIS_ALG.GER_KET_VERM 

52D8 

HEAT EXCH 

actual capacity 

kW 

M300  

M340  

  

WARMWIS_ALG.GEW_OPSLAG_VERM 

52DC 

HEAT EXCH 

Des forced storage capacity 

kW 

I340.2 Desired capacity of the exchanger that is calculated for the filling of the heat buffer in the active period. See Gedwongen opslag in warmtebuffer. 

M300  

M340 The desired storage capacity of the heat exchanger if the buffer strategy demands this (refer to I330.2 Heat power/Forced storage). 

  

WARMWIS_ALG.GEW_RESERV_VERM 

52DD 

HEAT EXCH 

Des reserve capacity 

kW 

M300  

M340 The desired reserve capacity of the heat exchanger if the heat reserve demands this. The heat reserve demands a capacity to meet an expected future heat demand. 

  

WARMWIS_ALG.KET_VERN_VRIJG 

52E1 

HEAT EXCH 

Heat surplus% 

M300.1 The heat surplus percentage of the heat exchanger. If the heat exchanger becomes too hot due to a forced demand, the heat surplus percentage increases. 

M340 The heat surplus percentage of the heat exchanger. 

  

WARMWIS_MEET.GEM_T_RET_WW 

5305 

HEAT EXCH 

Measured return temperature 

°C 

M340 The measured return temperature of the heat exchanger. 

  

WARMWIS_TOEST.TOESTAND 

5331 

HEAT EXCH 

status heat exchanger 

0=LIMITED 

1=READY 

2=PRE-RUN 

3=POST RUNNING 

4=MIN TIME ON 

5=ON 

6=ERROR 

  

I340 Status of the heat exchanger 

M300.1 Indication of the status of the heat exchanger. See 13 Status HX 

M340 Indication of the status of the heat exchanger. 

  

WARMWIS_VERM.GEW_WARM_VERM_W 

533D 

HEAT EXCH 

Des heating capacity 

kW 

M300 The total demanded heat capacity from the heat exchanger. 

M340 The desired heat capacity of the heat exchanger. This is the sum of the desired greenhouse capacity and the internal capacity. 

  

WASROBOT.BEPERKING 

5352 

WASH ROBOT 

Limitation 

0=NONE 

1=NO RELEASE 

2=WIND 

3=TEMP 

4=WIND/TEMP 

5=MAN OFF 

  

I240 Present limitation of the wash robot. 

M240 See 12 Limitation . 

  

WASROBOT.ROBOT_TOEST 

535C 

WASH ROBOT 

Status wash robot 

0=OFF 

1=REST 

2=WAIT RELEASE 

3=START 

4=OPERATION 

5=ERROR 

  

I240  

M240 See 11 Status wash robot . 

  

FILTER.FILTER_BEPERK 

5395 

FILTER 

filter limitation 

0=NONE 

1=CONSUMPTION MAX 

2=CONSUMPTION MIN 

3=START ERROR 

4=EXT ERROR 

5=DIRTY 

  

M430.1  

M431  

  

FILTER.FILTER_TOESTAND 

5397 

FILTER 

filter status 

0=REST 

1=RECIPE 

2=START 

3=CLEANING BACK W 

4=ERROR 

5=RINSE 

6=OPERATION 

7=O & CLEANING 

8=LIMIT FLOW 

  

M430 The status of the filter rinse. 

M430.1  

M431  

  

TEMP_M.GEM_TEMP 

5488 

WAT SYS 

Measured water temperature 

°C 

I432 Temperature of the water of which the EC is measured. The EC depends on the temperature and must be corrected for this. 

  

VialuxFlow.CalculatedFlow 

551F 

UV SYSTEM 

Calculated flow 

m³/hr 

M450  

  

VialuxFlow.MeasuredFlow 

5601 

UV SYSTEM 

Measured flow 

m³/hr 

M450  

  

VialuxSystem.CalcUVdosage 

55CC 

UV SYSTEM 

Calculated UV 

mJ/cm² 

M430.1  

M450 The calculated UV dosage. 

  

VialuxSystem.Limitation 

65DC 

UV SYSTEM 

Limitation 

0=NONE 

1=CONTROL OFF 

2=RELEASE SETTING 

3=RELEASE EXTERNAL 

4=UV DOSAGE 

5=LAMP COOL DOWN 

6=FLOW DEFECTIVE 

7=CHAMBER HOT 

8=FLOW TOO LOW 

9=FLOW TOO HIGH 

10=START UV 

11=DOS TOO LOW 

12=LAMP OFF 

16=WIPER OUT 

17=WIPER IN 

18=WIPER MOTOR 

19=WIPER CONTACT 

20=ERROR 

21=I UV SENSOR 

22=I WIPER OUT 

23=I WIPER HOME 

24=I WIPER CTL 

25=I WIPER THERM 

26=I V5 DISINFECTED 

27=I ERROR 

28=I RELEASE 

29=I ACID TANK 

30=I TEMP 

31=I LAMP 

35=EXPOSURE TIME 

36=WIPER MAN OPER 

37=WIPER HOME ER 

38=V5 DISINFECTED 

39=T10 TOO LOW 

40=I POWER FAILURE 

41=POWER FAILURE 

50=TRANSLUCENCY 

51=PEROXIDE 

52=ACID 

53=TYPE UV CHAMBER 

54=DISINFECT 

55=PURIFY 

56=CONFIGURATION 

57=ACID RINSE 

58=PUMP OFF 

59=DOSAGE 

60=I V5 PURIFIED 

61=V5 PURIFIED 

  

I453 The limitation of the UV system. See Limitation. 

M430.1  

M450  

  

VialuxSystem.MeasUVdosage 

55B4 

UV SYSTEM 

UV dos. 

mJ/cm² 

M430.1  

M450 The measured UV dosage that has been calculated from the measured intensity (measured by the UV sensor) and the measured flow. This means it is a good measurement for the UV dosage. 

  

VialuxSystem.ProcessState 

55EA 

UV SYSTEM 

Status 

0=REST 

1=START 

2=PRODUCTION 

3=ACID RINSE 

4=ERROR 

5=POST RUNNING 

  

I453 The status of the UV system. See Status . 

M430.1  

M450 The status of the UV system. 

  

VialuxSystem.StatusLamps 

5555 

UV SYSTEM 

Lamp status 

0=OFF 

1=LOW 

2=MID 

3=HIGH 

4=COOL DOWN 

  

I453 The status of the lamp. 

M450 The status of the lamp: OFF, LOW, MIDDLE, HIGH or COOL DOWN. 

  

VialuxSystem.Translucency 

55BF 

UV SYSTEM 

Translucency 

M450 The translucency indicates the level of the measured UV-C intensity in respect of the measured UV-C intensity of a cleaned tube. 

  

DOS_CTL.BEPERKING 

5660 

WAT SYS 

dosage limitation 

0=NONE 

1=CHANNEL 

2=MIXING TANK 

3=EXTERNAL 

4=pH CALIB 

5=ECs SNS 

6=EC SNS 

7=pH SNS 

8=CTR pH ↓ 

9=CTR pH ↑ 

10=CTR EC ↑ 

11=CTR EC ↓ 

12=RCP pH ↓ 

13=RCP pH ↑ 

14=RCP EC ↑ 

15=RCP EC ↓ 

16=FINE TUNING 

17=NUTRONIC 

18=CONNECTION 

  

M420  

M430.1  

  

DOS_CTL.TOESTAND 

5665 

WAT SYS 

dosage status 

0=REST 

1=CHECK 

2=START 

3=OPERATION 

4=RESET 

5=ERROR 

6=NUTRONIC 

  

I420 Status of the dosage. 

M420  

M430 The status of the dosage. 

M430.1  

  

DOS_EC_CTL.REGEL_EC 

5667 

WAT SYS 

calculated EC 

mS/cm 

M420  

M430.1  

  

DOS_PH_CTL.REGEL_PH 

5669 

WAT SYS 

calculated pH 

pH 

M420  

M430.1  

  

EC_BOX.GEM_EC 

56A9 

WAT SYS 

EC 

mS/cm 

M420  

M430 The measured EC value. 

M430.1  

  

EC_M_SENSOR.GEM_EC 

56AE 

WAT SYS 

EC supply 

mS/cm 

M420  

M430 The measured EC value of the supply water. 

M430.1 The measured EC value of the supply water. 

  

EC_VR.BER_EC_VR 

56B2 

WAT SYS 

calculated EC supply 

mS/cm 

M420  

M430.1 The calculated EC value of the supply water. 

  

GIETWVER.GEM_TEMP 

5709 

WAT SYS 

irrigation water temperature 

°C 

I423 Temperature of the irrigation water. 

M420  

M430 The temperature of the irrigation water. 

M430.1  

  

PH_BOX.GEM_PH 

5752 

WAT SYS 

pH 

pH 

M420  

M430 The measured pH value. 

M430.1  

  

VialuxCascade.CascadeActCap 

577B 

WAT SYS 

Actual capacity 

m³/hr 

I453  

  

VialuxCascade.CascadeDesireCap 

577D 

WAT SYS 

Desired capacity 

m³/hr 

I453 The desired capacity of the UV systems. 

  

WATDIS.BEPERKING 

5787 

WAT SYS 

water system limitation 

0=NONE 

7=DOSAGE 

8=IRR W HEAT 

9=EC SUPPLY 

10=WATER MIX 

11=SYST PUMP 

12=CONSUMP 

13=SET WAIT 

14=EXT WAIT 

15=UV SYSTEM 

41=RETURN 

42=DESTINATION TANK 

43=RECYCLE TANK 

44=FRESH WATER TANK 

45=OVER DEM 

46=MAX CAPACITY 

47=VALVE GROUP CHANGE 

48=RECIPE CHANGE 

49=RINSE VALVE CHANGE 

50=EXTERN WATER TR. 

51=RETURN PIT ON MAX 

  

I430 Limitation of the water system. 

M430.1  

  

WATDIS.BER_FLOW 

5788 

WAT SYS 

calculated flow 

m³/hr 

M420  

M430 The expected flow is determined by the total capacity of all active valves of the water system. 

M430.1  

  

WATDIS.FLOW 

578E 

WAT SYS 

water flow water irrigation 

m³/hr 

M420  

M430 The measured flow for the irrigation. 

M430.1  

  

WATDIS.RECEPT_NR 

579A 

WAT SYS 

recipe 

  

M430 The recipe number that is presently active, or the recipe that was used during the last irrigation cycle. 

M430.1  

  

WATDIS.TOESTAND 

57A5 

WAT SYS 

water system status 

0=REST 

1=CHECK 

2=PRE-RUN 

3=OPERATION 

4=ERROR 

5=WAIT 

6=FILTER 

7=UV SYSTEM 

8=BLOCKED 

  

I430 Status of the water system. 

M430 See: I430 Storing watersysteem/Reset & halt. 

M430.1  

M440 The status of the water system. 

  

CO2wk_Prod.CdactBer 

5821 

CHP 

CO₂ production active 

0=NO 

1=YES 

  

M250  

M330.1 Indication whether there is CO2 dosage with the CHP. 

  

VERM_M_UI.VE_GEM 

58D8 

CHP 

Measured electr. capacity 

kW 

M200 The actual electrical capacity of the CHP, which is determined by measuring the electrical production. 

  

WK_ELB.AAN_VERM_BRON 

58E1 

CHP 

Electrical capacity on 

kW 

M200 Capacity limit above which the CHP is activated for electricity demand. Even if the CHP is already active for a heat, CO₂ or storage demand, the electricity demand on the CHP must be greater than this limit before the CHP can start to supply electricity to the management. The lighting system can only be switched on after this. 

  

WK_ELB.BEPERKING 

58E5 

CHP 

Limitation 

0=NONE 

1=BLOCK 

2=RELEASE 

3=CHP 

4=MAX GAS 

5=STRATEGY 

6=UNBALANCED OFF 

7=COOLING WATER 

8=ELECTR.PROD 

  

M200  

  

WK_ELB.BRON_PRODUCEERT 

58E8 

CHP 

Electricity production active 

0=NO 

1=YES 

  

M200 Indication whether the electricity production by the CHP is active. 

  

WK_ELB.GER_CAP_BRON 

58F2 

CHP 

Max electrical capacity 

kW 

M200 The maximum electrical capacity to be supplied by the CHP. 

  

WK_ELB.GEW_EXTERN_AAN 

58F3 

CHP 

Des electrical capacity 

kW 

M300 The desired electrical capacity of the CHP, determined by an electricity demand from the electricity management. 

M330 The desired electrical capacity for the CHP, determined by an electricity demand from the electricity management. 

  

WK_ELB.VE_WK_VOLBESCH 

5900 

CHP 

actual electricity capacity CHP fully available 

kW 

M200 If the measured actual capacity (see Act electrical capacity ) rises above the limit shown here, the CHP is fully available to supply electricity to the electricity consumers such as lighting systems and electrical consumers. 

  

WK_SYS.BEPERKING 

590C 

CHP 

limitation CHP 

0=NONE 

1=TOO WARM 

2=ERROR 

3=RELEASE 

4=NOT AVAILABLE 

5=MANUAL 

6=MAX GAS 

7=UNBALANCED OFF 

8=COOLING WATER 

9=PART LOAD 

10=ELECTR. RELEASE 

  

I330 The limitation of the CHP, see M330 Warmtekracht/Overzicht. 

M250.1 Report of the limitation of the CHP. See M300.1 HT-warmtebeheer - HT-bronnen. 

M300.1 The limitation of the CHP. 

M330 The limitation of the CHP. 

  

WK_SYS.GEM_AANV_TEMP 

5918 

CHP 

measured supply temperature 

°C 

M300.1 The measured supply temperature of the CHP. 

M330  

  

WK_SYS.GEM_RET_TEMP 

5919 

CHP 

measured return temperature 

°C 

M300.1 The measured return temperature of the CHP. 

M330  

  

WK_SYS.GER_KET_VERM 

591B 

CHP 

CHP heat capacity control 

kW 

I330 Actual heat power by the CHP. 

M300  

M330  

M330 The actual heat capacity from this CHP. 

  

WK_SYS.GEW_EXTERN_VERM 

591C 

CHP 

Des external capacity 

kW 

I330.1 Desired external capacity demand to the CHP. 

M300 The desired capacity when the CHP is controlled to switch on because of an external demand (for example an external electricity demand). 

M330 The desired capacity when the CHP is controlled because of an external demand (for example an external electricity demand). 

  

WK_SYS.GEW_OPSLAG_VERM 

591F 

CHP 

Des forced storage capacity 

kW 

I330.2 Desired capacity of the CHP that is calculated for the filling of the heat buffer in the active period. See Gedwongen opslag in warmtebuffer. 

M300  

M330 The desired capacity of the CHP if the buffer strategy demands this (refer to I330.2 Heat power/Forced storage). 

  

WK_SYS.KET_VERN_VRIJG 

5921 

CHP 

Heat surplus% 

M300.1 The heat surplus percentage of the heat exchanger. If the heat exchanger becomes too hot due to a forced demand, the heat surplus percentage increases. 

M330 The heat surplus percentage that is present with this CHP. 

  

WK_SYS.TOESTAND 

5931 

CHP 

status CHP 

0=OFF 

1=ON 

2=MIN TIME OFF 

3=MIN TIME ON 

4=DELAY OFF 

5=DELAY NEXT ON 

6=DELAY NEXT OFF 

7=TOO COLD 

9=DELAY ON 

  

I330 The status of the CHP, see M330 Warmtekracht/Overzicht. 

M250.1  

M300.1 Indication of the status of the CHP. 

M330 Indication of the status of the CHP. 

  

WK_SYS.WK_EXT_BLOK_ACT 

593B 

CHP 

External blocking 

0=NO 

1=YES 

  

M330 Indication that the external blocking is active. 

  

WK_SYSTEEM.GEW_CO2_VERM 

594A 

CHP 

desired CO₂ capacity 

kW 

M300 The desired CO2 capacity of the CHP. 

M330 The desired CO2 capacity for the CHP, because of a demand to CO2 from the CO2 management. 

  

WK_SYSTEEM.GEW_CONS_VERM 

594B 

CHP 

desired greenhouse capacity 

kW 

M300  

M330 The desired heat capacity that has been allocated to this CHP because of a capacity demand from the compartments. 

  

WK_SYSTEEM.GEW_RESERV_VERM 

594E 

CHP 

Des reserve capacity 

kW 

M300  

M330 The desired reserve capacity of the CHP if the heat reserve demands this. The heat reserve demands a capacity to meet the expected future heat demand. 

  

Lichtuitstoot.Percentage 

5A8F 

  

Calculated maximum light emission 

I207 Maximum permitted light emission. Dependent on the I168 Curtain/Control setting, line 17: Light emission: min. curtain position the curtain is controlled to a minimum curtain position.