To use the manual overrides functionality, you need the permission ‘Manage overrides’ in Access Control.
The new Manual overrides tab in Building Operator provides an easy way to manage the overrides in the system. You can create, change or remove software overrides for any data point.
Override indicator : The hand icon indicates that a data point has an active manual override.
Hardware value column: In this column, you can view the hardware value of a data point. For safety reasons, hardware overrides can only be set or reset on the physical controller itself.
Software value column: In this column, you can view the software value of a data point and create and change an override. Overrides can be reset to 'Automatic' with the reset button. The software override is then removed.
Active overrides switch: Use this switch to only show the data points that are manually overridden.